NC20 - Manual - 01 - 2015
FUNCTION CHARACTERISTICS
Residual overcurrent - 50N/51N
Preface
Three operation thresholds, independently adjustable (
I
E
>,
I
E
>>,
I
E
>>>) with adjustable delay (
t
E
>,
t
E
>>,
t
E
>>>).
The fi rst one (
I
E
>) may be programmed with defi nite or inverse time according the IEC and ANSI/IEEE
standard.
The second and third thresholds (
I
E
>>,
I
E
>>>) with independent time.
For each threshold a reset time can be set (
t
E>RES
,
t
E>>RES
,
t
E>>>RES
) useful to reduce the clearing
time for intermittent faults.
The fi rst threshold trip may be inhibited by start of the second and/or third threshold (
I
E
>>,
I
E
>>>).
Similarly the second threshold trip may be inhibited by start of the third threshold (
I
E
>>>).
Operation and settings
The residual fundamental frequency current
I
EC
, calculated from the vector sum of the three phase
currents, is compared with the setting value. Current above the associated pickup value is detected
and a start is issued. After expiry of the associated operate time a trip command is issued; if instead
the current drops below the threshold, the element is restored.
The fi rst threshold (
I
E
>) may be programmed with defi nite or inverse time according the following
characteristic curves:
Standard Inverse Time (IEC 255-3/BS142 type A or SIT):
t
= 0.14 ·
t
E
>
inv
/ [(
I
EC
/
I
E
>
inv
)
0.02
- 1]
Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t
= 13.5 ·
t
E
>
inv
/ [(
I
EC
/
I
E
>
inv
) - 1]
Extremely Inverse Time (IEC 255-3/BS142 type C or EIT):
t
= 80 ·
t
E
>
inv
/ [(
I
EC
/
I
E
>
inv
)
2
- 1]
Moderately Inverse (ANSI/IEEE type MI):
t
=
t
E
>
inv
· {0.01 / [(
I
EV
/
I
E
>
inv
)
0.02
- 1] + 0.023}
Very Inverse (ANSI/IEEE type VI):
t
=
t
E
>
inv
· {3.922 / [(
I
EC
/
I
E
>
inv
)
2
- 1] + 0.098}
Extremely Inverse (ANSI/IEEE type EI):
t
=
t
E
>
inv
· {5.64 / [(
I
EC
/
I
E
>
inv
)
2
- 1] + 0.024}
Where:
t
: operate
time
I
EC
: calculated
residual
current
I
E
>: threshold
setting
t
E
>
inv
: operate
time
setting
For all inverse time characteristics, following data applies:
Asymptotic reference value (minimum pickup value): 1.1
I
E
>
Minimum operate time:
0.1 s
Range where the equation is valid:
[1]
1.1 ≤
I
EC
/
I
E
> ≤ 20
If
I
E
> pickup ≥ 2.5
I
n
, the upper limit is 50
I
n
For all defi nite time elements the upper limit for measuring is 50
I
n
.
All residual overcurrent elements can be enabled or disabled by setting
ON
or
OFF
the
IE> En-
able
,
IE>> Enable
and/or
IE>>> Enable
parameters inside the
Set \ Profi le A(or B) \ Residual
overcurrent-50N/51N \
IE> Element
(
IE>> Element
,
IE>>> Element) \ Setpoints
menus.
The fi rst overcurrent element can be programmed with defi nite or inverse time characteristic by
setting the
IE>Curve
parameter (
DEFINITE, IEC/BS A, IEC/BS B, IEC/BS C, ANSI/IEE
MI, ANSI/IEE VI, ANSI/IEE EI
) available inside the
Set \ Profi le A(or B) \ Residual overcurrent-
50N/51N \
IE> Element \ Setpoints
menu.
The trip of
I
E
> element may be inhibited by the start of the second and/or third el-
ement (
I
E
>>,
I
E
>>>) by setting
ON
the Disable IE> by start IE>>, Disable IE> by
start IE>>> (
IE>disbyIE>>, IE>disbyIE>>>
) parameters available inside the
Set \ Profi le A(or B) \ Residual overcurrent-50N/51N \ IE>> Element
(
IE>>> Element) \ Setpoints
Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point
•
•
•
•
•
•
•
•
•
•
t-int-F50N-51N.ai
I
EC
I
E
>>
I
E
>>>
t
E
>
t
E
>>
t
E
>>>
I
E
>
t
TRIP
General operation time characteristic for the residual overcurrent elements - 50N/51N