NC20 - Manual - 01 - 2015
APPENDIX
200
200
NC20 - Manual - 01 - 2015
APPENDIX
Description
Parameter Unit
Setting range
Disabling Dth> by 50-51 start
Dth>disby50-51
OFF | ON
Dth> Trip relays
Dth>-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Dth> Trip LEDs
Dth>-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Phase overcurrent - 50/51 RMS
I>AL Element
Setpoints
I>AL Enable
I>AL Enable
OFF | ON
ICLP>AL Mode
ICLP>AL Mode
OFF | ON - Element blocking | ON - Change setting
ICLP>AL Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I>AL Logical block
I>ALBLK1
OFF | ON
I>AL Start relays
I>ALST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I>AL Trip relays
I>ALTR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I>AL Start LEDs
I>ALST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
I>AL Trip LEDs
I>ALTR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
50/51 Alarm threshold defi nite time
State
OFF | ON
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I>ALdef within CLP
ICLP>ALdef
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
I>ALdef Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 99.9 step = 0.1
100 ... 200 step = 1
I> Element
Setpoints
I> Enable
I> Enable
OFF | ON
I> Curve type
I>Curve
IEC/BS A | IEC/BS B | IEC/BS C | ANSI/IEEE MI
| ANSI/IEEE VI | ANSI/IEEE EI | CAPACITOR |
DEFINITE
ICLP> Mode
ICLP> Mode
OFF | ON - Element blocking | ON - Change setting
ICLP> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
I> Logical block
I>BLK1
OFF | ON
I> Input selective block
I>BLK2IN
OFF | ON
I> Output selective block
I>BLK2OUT
OFF | ON
I> Breaker failure
I>BF
OFF | ON
I>AL Disabling by I>
I>ALdisbyI>
OFF | ON
I> Start relays
I>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I> Trip relays
I>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
I> Start LEDs
I>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
I> Trip LEDs
I>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
50/51 First threshold defi nite time
State
OFF | ON