216
216
NC20 - Manual - 01 - 2015
APPENDIX
216
216
NC20 - Manual - 01 - 2015
APPENDIX
Description
Parameter Unit
Setting range
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 9.99 step = 0.01
10.0 ... 40.0 step = 0.1
I>>>def within CLP
ICLP>>>def
In
0.100 ... 0.999 step = 0.001
1.00 ... 9.99 step = 0.01
10.0 ... 40.0 step = 0.1
I>>>def Operating time
Value
s
0.03 ... 10.00 step = 0.01
Residual overcurrent - 50N/51N
IE> Element
Setpoints
IE> Enable
IE> Enable
OFF | ON
IE> Curve type
IE>Curve
IEC/BS A | IEC/BS B | IEC/BS C | ANSI/IEEE MI |
ANSI/IEEE VI | ANSI/IEEE EI | DEFINITE
IECLP> Mode
IECLP> Mode
OFF | ON - Element blocking | ON - Change setting
IECLP> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
tE> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IE> Logical block
IE>BLK1
OFF | ON
IE> Input selective block
IE>BLK2IN
OFF | ON
IE> Output selective block
IE>BLK2OUT
OFF | ON
IE> Breaker failure
IE>BF
OFF | ON
IE> Start relays
IE>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IE> Trip relays
IE>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IE> Start LEDs
IE>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
IE> Trip LEDs
IE>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Defi nite time
50N/51N First threshold defi nite time
State
OFF | ON
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
IE>def within CLP
IECLP>def
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
IE>def Operating time
Value
s
0.04 ... 9.99 step = 0.01
10.0 ... 99.9 step = 0.1
100 ... 200 step = 1
Inverse time
50N/51N First threshold defi nite time
State
OFF | ON
Pickup value
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
IE>inv within CLP
IECLP>inv
In
0.100 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
IE>inv Operating time
tE>inv
s
0.02 ... 9.99 step = 0.01
10.0 ... 60.0 step = 0.1
IE>> Element
Setpoints
IE>> Enable
IE>> Enable
OFF | ON
IECLP>> Mode
IECLP>> Mode
OFF | ON - Element blocking | ON - Change setting
IECLP>> Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
tE>> Reset time delay