I
Page 31
installation, use and maintenance guide
Mon Amour
10 – SMOKE DISCHARGE TUBE AND VENTILATION OF THE ROOMS
10.1 FOREWORD
Due to the frequent accidents caused by poor functioning of flue outlets installed in private dwellings, we have prepared
the following paragraph to assist the installer in his inspection of the parts concerned with eliminating the gases
produced by combustion.
The smoke outlet must be fitted in compliance with standards UNI 7129/92, UNI 10683 and EN 14785 and it must
observe the reference values laid down in the standard, in particular, the outlet must comply with fire prevention
regulations. This chapter is not intended to replace these standards.
It is important to carefully follow the instructions included in these standards: failure to observe these
instructions could cause serious damage to the product, to the system, to objects and to persons using the
generator.
10.2 ROOM VENTILATION
CAUTION: the presence of extraction fans or similar appliances, if operating in the same room or space in which the
product is installed, could cause problems for the correct operation of the product.
CAUTION: do not obstruct the vents or the air inlets on the appliance.
The room where the appliance is installed must have a good air flow to guarantee air for the appliance for the combustion process
and for ventilation of the room. The natural air flow must take place directly through permanent openings on the outer walls or through
single or multiple ventilation ducting (paragraph 9.2.1).
The ventilating air must come from outside and if possible, away from sources of pollution. The openings in the walls must comply
with the following conditions:
• have an unobstructed section of at least 6cm² for each Kw of installed thermal power, with a minimum limit of 100cm²;
• be made in such a way that the vent openings, both on the inside and outside of the wall, cannot be obstructed;
• be protected with grills or similar systems that do not reduce the opening section indicated above;
• be situated at a height near floor level and they must not obstruct the correct operation of the combustion product discharge devices;
if this position is not possible the section of the ventilation openings must be enlarged by at least 50%.
10.2.2 VENTILATION OF THE ADJOINING ROOMS
The air flow can also be obtained from an adjacent room as long as:
• the adjoining room is equipped with direct ventilation in compliance with the paragraphs described above;
• only appliances connected to the exhaust pipe are installed in the room that is ventilated;
• the adjoining room is not used as a bedroom or a common area of the building;
• the adjacent room is not a room with a fire hazard, such as storage sheds, garages, combustible material store rooms, etc...;
• the adjoining room does not become a vacuum compared to the room to be ventilated due to a reverse draught effect; (the reverse
draught can be caused by the presence in the room of either another heating appliance running on any type of fuel, a fireplace, or
any suction device, which have not been provided with an air intake);
• the air flow from the adjoining room to the room to be ventilated is unobstructed through the permanent apertures having an overall
net section of no less than that indicated above. These apertures can be obtained by enlarging the space between the door and the
floor.
10.2.1 SINGLE OR MULTIPLE VENTILATION DUCTING
If the combustion air is supplied through pipes, the available draught, produced by the installed appliance in use and by the
corresponding combustion product evacuation system, must be greater than the sum of the resistance offered by the pipes (frictional
resistance, resistance due to direction changes, cross-sectional restrictions, etc...).
The single ventilation pipes can be vertically and horizontally oriented: the length of the horizontal sections must be reduced to a
minimum.
The connectors between pipes with different orientations must not have any reduced cross-sections with sharp bends.
The angle of connection between the axes of two successive pipes must not be less than 90°.
For combustion air supplied through branched pipes, the sum of the resistance offered by the pipes (frictional resistance, resistance
due to direction changes, cross-sectional restrictions, etc....) can be a maximum of 10% of the available draught, produced by the
various appliances in use installed on the various floors and by the combustion product evacuation system.
The branched ventilation pipes must be vertically-oriented with an uphill run.
The inlet vent to the room to be ventilated must be located down low and in a position where it does not interfere with the discharge
of combustion products and must be protected by a grill or similar device.
10.3 SMOKE OUTLET
The smoke channel, the exhaust pipe, chimney and flue outlet (defined as the system for the evacuation of combustion
products), are parts of the heating system and they must comply with the legislative requirements of the Ministerial
Decree DM 37/08 (ex Italian Law 46/90) and to the applicable specific installation regulations, according to the type of
fuel. Fireplaces, stoves and barbecues must not be installed in locations where gas appliances type A and type B are