Refrigeration Maintenance (Rev 6/98)
75
CHECKING COMPRESSOR OIL
The compressor oil should be checked when there is evi-
dence of oil loss (oil leaks) or when components in the
refrigeration system have been removed for service or
replacement.
Checking Compressor Oil
To check compressor oil level with an ambient air
temperature above 10° C (50° F):
Install a gauge manifold on the compressor.
Operate the unit on Cool with a 138 kPa (20 psi) minimum
suction pressure and a 1275 kPa (185 psi) minimum dis-
charge pressure for 15 minutes or more.
After the unit has maintained the above conditions for 15
minutes, observe the oil level. The oil should be 1/4 to 1/2
up in the sight glass.
1.
Sight Glass
1
To check compressor oil level with an ambient air
temperature below 10° C (50° F):
Run the unit through a complete defrost cycle. After com-
pleting the defrost cycle, run the unit on Cool for ten min-
utes. Observe the oil level. The oil should be 1/4 to 1/2 up in
the sight glass.
If the box is empty, you can run the unit on the heat cycle
instead of the defrost cycle.
NOTE: Use refrigeration compressor oil ONLY. Polyol
Ester type P/N 203-413 is required for R-402B, R-404A,
and R-134a.
HIGH PRESSURE CUTOUT SWITCH
(HPCO)
The HPCO is located on the compressor discharge mani-
fold. If the discharge pressure rises above 3103 kPa
(450 psi) [2068 kPa (300 psi) for R-12 and R-134a sys-
tems], the HPCO opens the 8D circuit to shutdown the unit.
To test the HPCO, rework a gauge manifold following the
High Pressure Cutout Manifold illustration.
1.
Connect the gauge manifold to the compressor dis-
charge service valve with a heavy duty, black jacketed
thick wall #HCA 144 hose with a 6204 kPa (900 psi)
working pressure rating.
2.
Run the unit in high speed cool.
Summary of Contents for Super II SR+
Page 4: ......
Page 10: ...ii ...
Page 14: ...4 ...
Page 22: ...Unit Description Rev 6 98 12 Front View AEA1350 ...
Page 23: ...Unit Description Rev 6 98 13 Right Side Door Open AEA1351 ...
Page 24: ...Unit Description Rev 6 98 14 Left Side Doors Open AEA1352 ...
Page 26: ...Operating Instructions Rev 6 98 16 Control Box Cover AEA1354 ...
Page 34: ...24 ...
Page 42: ...Electronic Controls Rev 6 98 32 SOFTWARE REVISION 04XX ALARMS AEA1358 ...
Page 82: ...72 ...
Page 90: ...80 ...
Page 116: ...106 ...
Page 120: ...110 ...
Page 130: ...120 ...
Page 141: ...131 Schematic Diagram SBIII SII RMNII 30 SR MPIV ...
Page 142: ...132 Wiring Diagram SII SBIII RMN30 SR MPIV Page 1 of 4 ...
Page 143: ...133 Wiring Diagram SII SBIII RMN30 SR MPIV Page 2 of 4 ...
Page 144: ...134 Wiring Diagram SII SBIII RMN30 SR MPIV Page 3 of 4 ...
Page 145: ...135 Wiring Diagram SII SBIII RMN30 SR MPIV page 4 of 4 ...