Troubleshooting
LED is Red
A red LED indicates only that a fault (or alarm) has occurred and does not necessarily
indicate that reception has stopped. A flashing red light indicates a minor alarm and a
solid red light indicates a major alarm. You can communicate with the Rx 1+1 system
to determine what is causing the fault, and then clear the fault condition.
1. Establish communication with the Rx 1+1 system by using any of the M&C inter-
faces.
2. View the Alarm tab (shown on
) to determine the current alarm.
3. View the Sensor tab (shown on
) to determine which sensor reading
caused the alarm.
4. Compare your readings to the thresholds.
5. Adjust the threshold level to bring the reading within specifications and thus clear
the fault.
When the fault is cleared, the LED should be flashing green.
Repair Policy
Terrasat products are not field repairable.
In the event that a failure has been detected, it might be necessary to return the
defective unit to the factory or a factory-authorized service center. The following
section contains instructions for returning a defective unit to the factory for repair.
Returned Material Authorization (RMA)
If any equipment is determined to be defective:
•
Have the following information available:
•
Unit serial number
•
Unit part number and description
CAUTION
Never disconnect RF cables or connectors
associated with a transmitter in operation
since this may result in an RF burn through
contact with RF conductors.
Summary of Contents for Rx 1+1
Page 1: ...Receive Redundant Systems Operations Manual 24 Hour Technical Support 1 408 782 2166 ...
Page 6: ...iv ...
Page 10: ...viii This page intentionally left blank for double sided printing ...
Page 12: ...x This page intentionally left blank for double sided printing ...
Page 20: ...1 6 Introduction This page intentionally left blank for double sided printing ...
Page 36: ...2 16 Functional Description This page intentionally left blank for double sided printing ...
Page 84: ...6 6 Troubleshooting This page intentionally left blank for double sided printing ...
Page 145: ...Screen Shots E 13 IDC Low Threshold Sets the lowest permitted level down to 100 Ma ...
Page 158: ...E 26 Web Pages This page intentionally left blank for double sided printing ...
Page 161: ...Reference Drawings F 3 Figure F 2 Fabrication Drawing FBD 20786 XXXX Rev A ...
Page 163: ...Reference Drawings F 5 Figure F 4 Top View of Rx 1 1 System Showing Connector Locations ...