June 2009
Section 4 • Repair Procedures
4 - 12
GS-30 • GS-32 • GS-46
Part No. 96316
REV D
PLATFORM CONTROLS
1-4
Software Configuration
(after serial numbers GS3005-74999,
GS3205-74999 and GS4605-74999)
The Electronic Control Module (ECM) contains
programming for all configurations of the Genie
GS-30, GS-32 and GS-46. The machine can be
adjusted to a different configuration using the
buttons at the platform controls.
How to Determine the
Software Configuration
1 Remove the platform controls from the platform.
2 Pull out the red Emergency Stop button to the
on position at the ground controls.
3 Push in the red Emergency Stop button to the
off position at the platform controls.
4 At the platform controls, press and hold the lift
function select and speed select buttons, and
pull out the red Emergency Stop button to the
on position.
Result: The diagnostic display, at the platform
controls and the ECM, will show "SC."
a
lift function select button BN9
b
diagnostic display
c
red Emergency Stop button P2
d
drive function select button BN8
5 Release the lift function select and speed select
buttons.
Result: The diagnostic display will show the
current configuration.
5 Push in the red Emergency Stop button to the
off position at both the ground and platform
controls and turn the key switch to the off
position.
Machine Option Definitions
Motion Alarm:
The motion alarm will sound when operating any function.
Lift/Drive Cut Out:
In addition to an alarm sounding, lift and drive functions are disabled when the
platform is raised above the down limit switch and the incline of the chassis exceeds the rating on the
serial plate. Configured on all machines.
Platform Overload:
When the platform overload limit switch is tripped, signaling an overload condition
in the platform, all machine functions are disabled. The additional weight must be removed from the
platform and the power cycled from off to on before any function can be resumed. Required for CE
models.
Descent Delay:
This option halts descent for 4 to 6 seconds. All controls must be released and re-
engaged before descent is re-enabled. Required for CE models.
Battery Drain Alarm:
When the machine is turned on and in the stowed position, and no function is
activated for 2 minutes, an alarm will sound once every 3 seconds.
When this option is configured, a dot in the diagnostic display window will remain continuously
illuminated when the ECM is in the 'SC' mode OR when the platform up function is activated.
a
c
b
d