(A) DELIVERY
(1)
Equipment is purchased F.O.B. Factory and is the responsibility of receiving party to inspect unit
upon arrival at the destination before unloading or moving unit to its permanent location; inspect
closely for damage which may have been caused in transit. Report damage to delivering carrier
promptly (list damage or shortage on freight bill if possible). If damage is noted or discrepancies
found, the local Temtrol, Inc. sales representative should be notified immediately so that
corrective action may be instigated. Where local repairs or alterations are required, the
representative should be fully informed by the contractor as to the extent and expected cost of
work
required.
Unauthorized back-charges will not be recognized by Temtrol, Inc.
(B) STORAGE
(1)
Should storage of unit be required caution should be taken to set unit relatively level and in clean
location to protect motor, bearings, coils, filters and etc. from excessive dust. Also avoid storage in
location where children play and/or public access.
Air handling units should not be used as on site
storage for other mechanical trades.
If units are to be stored for an extended period of time the
following maintenance procedures must be performed:
a.
Fan wheels should be rotated by hand every 30 days.
b.
Each month bearings should be purged with new grease to remove
condensation.
c.
Before start-up new grease must be added to the bearings
d.
Belts should be removed, then prior to start-up, inspect and replace if necessary,
reinstall belt.
e.
All openings and access doors must remain sealed during storage.
f.
Dampers must be cleaned and lubricated prior to start-up.
g.
Extended storage could result in condensation on the inside of the unit.
Affected areas should be cleaned and dried prior to start-up.
Temtrol, Inc.