O-ITF-07
Page
14
(11)
FILTER ASSEMBLY
- tracks should be checked for rail seal retention where required and all rails
should be cleaned annually to control dirt build-up, filter drag and dust by-pass during change
out of media. Dirty filters reduce the air volume handled by the unit, and thereby its capacity.
Unit should not be run without proper filters or fan motor overload, dirty coil and restricted air
flow will result. Proper media retainers should be used at all times to avoid possible media
"blow-out", which can cause blockage of air flow and/or damage rotating fan and motor parts.
Do not operate media beyond its rated capacities before change out or "blow-out" damage
can
result.
(12)
CASING AND ACCESS DOORS
- should be checked for leakage (air and/or water). Door gasket
must be in proper alignment and if damaged, should be replaced. Inside access panels must be
latched properly to avoid air recirculation.
Door Adjustment: (All adjustments must be made to all hinges at the same time)
X,Y: Left/Right and Up/Down adjustment;
A.
Loosen both 1/4” bolts with a 3/8” hex.
B.
Move door to desired position.
C.
Tighten both 1/4” bolts with a 3/8” hex.
Z: Compression Adjustment;
A.
Tighten set screw to compress.
B.
Loosen set screw to uncompress.
Larger Drawing
Located In The