PROBLEM
PROBABLE CAUSE
Coil Does Not Deliver
Lack of chilled water
Chilled water pump undersized or malfunctioning
Adequate Cooling
Dirty finned tubes
Vacuum or use air hose to gently clean dirt from
finned tubes
Coil undersized
Replace with larger coil
Coil Leaks
Crack in brazed connection
Repair brazed joint
Internal corrosion
Replace coil
Moisture on Walls
Excess capicity through
Check air flow through coil
Downstream of Cooling
cooling coil
Coil
Standing water in drain pan
See "Condensate Drain Pan" Section
V.A.V. unit (Low Volume Air
Verify that the air flow and water flow are synchronized
Flow - High Volume Water
Flow)
SOLUTION
TROUBLE SHOOTING GUIDES
COOLING COILS