4.4.2. Install Tamper Circuit and External Resistors
TeleEye RX supports tamper detection on all alarm inputs including arm/disarm input, security switch
input, system tamper and power failure input.
DEOL
: Dual End of Line termination with NC and NO connection
SEOL
: Single End of Line termination with NC and NO connection
NC/NO
: Alarm and other input ports without tamper detection circuit connection
For example: By connecting the tamper circuit with DEOL, the circuit is in the normal close condition if
the resistance between point A and B detects 1.2kΩ (shown as below), whereas the circuit is in normal
open condition if the resistance between point A and B detects 7.2kΩ. The resistance transition from
1.2kΩ to 7.2kΩ is generated by an alarm tamper event for normal close circuit. The setup configuration of
those alarms and input ports are shown in the following diagrams. The circuit debouncing time between
each sensor is 20 milliseconds.
Dual End of Line Configuration
Normal Close (NC)
Normal Open (NO)
Term
Status
Description
S/C
Tamper
Wire short (point A and B)
LoZ
Normal
Sensor drive output close
(point B and C)
HiZ
Alarm
Sensor drive output open
(point B and C)
O/C
Tamper
Wire open (point A and B)
Term
Status
Description
S/C
Tamper
Wire short (point A and B)
LoZ
Normal
Sensor drive output close
(point B and C)
HiZ
Alarm
Sensor drive output open
(point B and C)
O/C
Tamper
Wire open (point A and B)
Summary of Contents for RX800 Series
Page 1: ...RX800 Series Ultra high Resolution Video Recording Server RX806 RX812 RX816 User Guide...
Page 2: ......
Page 25: ...10 Live video is shown after successful connection...
Page 127: ...Save Save the access rights when server startup or local user log out...
Page 154: ...3 Select sureLINK Registration Click on sureLINK Address Registrations...
Page 169: ......