4.4.3.7.
Power Failure
It is an input to the video recording server typically used for wiring the output signal pin from an
uninterruptible power supply (UPS).
Sensor Type
If the power failure input circuit type is normal close (NC), when the state of the circuit is opened, it
indicates power failure of TeleEye RX, while nothing happens when the state of the circuit is closed. If
the alarm sensor input circuit type is normal open (NO), when the state of the circuit is closed, it indicates
power failure of TeleEye RX, while nothing happens when the state of the circuit is open.
Physical Configuration for Power Failure Input
The power failure input and ground of TeleEye RX video recording server need to connect to an universal
power supply circuit UPS in order to detect any power failure condition.
The UPS circuit setup above is used as an example. Not all UPS have signal output. Some UPS have
self-testing for a period of time. Their signal output may toggle during test.
[
Main Menu
]
[
Event Handler
]
[
Power Failure
]
Enable
Enable / disable power failure event
Sensor Type
Select circuit open/close as normal state
Action
Set actions taken when power failure is detected