background image

2

Control Strategy

ZONING OPERATION  

In a multiple zone heating system, the zones may have different internal heat gains, heat losses or different temperature settings. Each
zone must therefore have individual temperature control. For maximum comfort, the heat should be continuously supplied to the zone
at the same rate the zone is losing heat. The most accurate method of accomplishing this is by outdoor reset; however, it is not normally
economical to modulate the supply water temperature to every zone.

Outdoor reset can be combined with zoning for a more cost effective solution. Through
indoor sensors, a zone control can provide indoor temperature feedback to the outdoor
reset control. The outdoor reset control will then adjust the supply water temperature to
satisfy the zone with the highest water temperature requirement. Heat to the remaining
zones will be cycled on and off by the zone control using zone valves or pumps. Since the
heat is cycled on and off, accurate PID control logic should be provided to maintain a stable
indoor temperature.

PID Zoning Logic  



Proportional (P)

In order to prevent indoor temperature swings, the heat supplied to each zone must be
proportional to the heat required by the zone. Proportional control logic can be
accomplished by pulse width modulation (PWM). A typical PWM system has a fixed
operating cycle. During this operating cycle, the on time of the zone relay is varied
based on the difference between the desired zone temperature and the actual zone
temperature. As the zone temperature drops, the relay on time increases and as the
zone temperature rises, the relay on time decreases.

Integral (I)

Controls that are strictly proportional suffer from a problem of offset. The amount of heat
supplied to the zone depends on how far the space temperature is below the desired
setpoint. This implies that as the heating load increases, the average room temperature
droops. On the coldest day of the year, the most heat is required and therefore the room
temperature must be coldest.
In order to overcome this offset, integral control logic is used. Only digital controls can provide integral control logic due to the lengthy
response time of buildings. Integral control logic is based on time. The longer the room temperature is below the desired setpoint,
the more heat is supplied to the room. With integral control logic, full heat can be supplied to the room on the coldest day of the
year without requiring that the room be cold.

Derivative (D)

In order to speed up the control’s response to quick changes in the heating load, derivative control logic is required. However,
sudden room temperature changes, for example from an open door or window, should be ignored by an intelligent control.

P + I + D = PID

If proportional, integral and derivative (PID) control logic are combined, the control is more able to prevent excessive temperature
swings and provide a stable room temperature under all conditions. It not only takes into account how much the room temperature
has drooped, but also how long there has been a droop and how fast the temperature is changing.

Zone Load Staggering 



In a multiple zone system, there can be sudden load changes on the boiler and system
due to multiple zones turning on or off. These sudden load changes often lead to boiler
short cycling and unnecessary mechanical stresses. The operation of the system can be
improved by staggering the starting points of each zone relay within the operating cycle.
Staggering of the zones maintains a relatively constant system flow rate which improves
boiler operation. Controlled staggering can also minimize boiler running time and improve
system efficiency when only a few zones are needed for short periods.

Zone Post Purge

 

Before the last zone is turned off in a heating cycle, the boiler is turned off but the zone continues to draw heat from the boiler. This
post purge of the boiler reduces stand-by losses and reduces overall energy consumption.

UNOCCUPIED (NIGHT SETBACK) 

During the night, or at times when people are not within the building, energy can be saved by lowering the building temperature for an
UnOccupied (Night Setback) period.

Due to the large thermal mass of buildings, it takes a long time for the indoor space temperature to significantly change whenever the
heating system is turned on or off. The building heat up or cool down time is further increased when high mass heating systems are
used (e.g. radiant floors). In most cases night setback cannot be used with these systems due to the long recovery time required in the
morning. A typical system is demonstrated in the diagram on page 3.

Zone 1

Zone 2

Zone 3

Zone 4

Post Purge

(Boiler off, Pump on)

On

On

On

On

On

70 

°

F

(21

°

C)

15 minutes

15 minutes

13 minutes

no heat

72 

°

F

(22

°

C)

68 

°

F

(20

°

C)

droop

70 

°

F

(22

°

C)

15 minutes

15 minutes

5 minutes

10 minutes

on

no heat

72 

°

F

(22

°

C)

68 

°

F

(20

°

C)

Heat

Source

90%

time on

85%

time on

100%

time on

M

M

M

Summary of Contents for Zone Control 367

Page 1: ...ngs pg 9 Technical Data pg 16 Advanced Sequence of Operation pg 10 Limited Warranty pg 16 Advanced Installation pg 12 Zone Control 367 One Two Stage One Stage Floating H1121 2 Made in Canada by tekmar...

Page 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Page 3: ...ontrol must base all Optimum Start Stopcalculationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and...

Page 4: ...agerelay and a Hi stage relay Example An RTU connected between the terminals Com Sen RTU 2 is used to control the output relays 1 and 2 Relay 1 is the Lo stage output relay and relay 2 is the Hi stage...

Page 5: ...re is no RTU or Indoor Sensor connected to terminals Com Sen RTU 1 5 6 the 367 can enable an auxiliary cooling control through output relay 1 Output relay 1 is turned on once the heating zones connect...

Page 6: ...ne valves or pumps If a zone valve or zone pump has not been operated in the past 3 days the 367 turns on the zone relay for 10 seconds Note The zone relay exercising time is increased to 3 minutes if...

Page 7: ...versed UnOccupied Switch Ifanexternaltimerorswitchisused connectthetwowiresfromtheexternaldrycontact switch to the UnO Sw Com Sen 14 and 16 terminals When these terminals short together the control re...

Page 8: ...the control If relay 4 is used connect the zone pump or zone valve circuit to the Com 3 4 4 22 and 24 terminals on the control If relay 1 is used for heating DIP switch set to Zone 1 Heating connect t...

Page 9: ...ction for the zone 1 relay If a zone pump or valve is connected to the terminals Com 3 4 4 22 and 24 follow a similar procedure as described above in the cooling section for the zone 1 relay If a zone...

Page 10: ...as soon as the Occupied period begins If the Optimum Start DIP switch is set to Off the 367 does not start raising the building temperature until the UnOccupied period ends More informa tion on the Op...

Page 11: ...367canoperateafananddampertobringoutsideairintothebuilding for free cooling An Indoor Sensor or RTU must be connected between terminals Com Sen RTU 1 and an Outdoor Sensor must be connected to Com Sen...

Page 12: ...nal on the actuating motor and the output relay 4 terminal 24 is connected to the close terminal on the actuating motor Common Block Com 5 6 If the Com 5 6 common block is used to control a floating a...

Page 13: ...eating zone Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 367 has a test routine which is used to test the main control functions The 367 continually...

Page 14: ...ct between Com 3 4 3 22 and 23 is closed and the device connected to this relay Open should be turned on Zone 4 Hi Stage The relay contact between Com 3 4 4 22 and 24 is closed and the device connecte...

Page 15: ...ctive Outdoor sensor open circuit design out off Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 short circuit RTU 2 short circuit RTU 3 short circuit RTU 4 short circuit...

Page 16: ...ry from state to state or province to province ProductReturnProceduresProductsthatarebelievedtohavedefectsinworkmanship or materials must be returned together with a written description of the defect...

Reviews: