background image

8

Sen — RTU 4 (8 and 10) terminals.

Common block for 

RTU 1 and RTU 2

DIP switch set to Zone 1 Heating
• If the common block is used for a single One Stage heating zone, connect the RTU or Indoor Sensor to terminals 

Com Sen

— 

RTU 1 (5 and 6).

• If the common block is used for 2 One Stage heating zones, connect one RTU to the 

Com Sen — RTU 1 (5 and 6) terminals

and connect the other RTU to the 

Com Sen — RTU 2 (5 and 7) terminals.

DIP Switch set to Zone 1 Cooling
• If the 367 is used to enable a cooling system, then no RTU or Indoor Sensor is

connected to terminal 

Com Sen — RTU 1 (5 and 6).

• If the 367 is used to control a cooling system the cooling RTU is connected to

terminals 

Com Sen — RTU 1 (5 and 6).

• If a single stage heating zone is connected to output relay 

2, connect the RTU or

Indoor Sensor to terminals 

Com Sen — RTU 2 (5 and 7).

Two Stage RTU and Indoor Sensor Connections

It is best to start the Two Stage heating zones at output relays 

1 and 2 and work towards

output relays 

5 and 6.

Common Block for 

RTU 1 and RTU 2

• If the common block is used for a Two Stage heating zone, connect the RTU or

Indoor Sensor to terminals 

Com Sen — RTU 2 (5 and 7).

Common Block for 

RTU 3 and RTU 4

• If the common block is used for a Two Stage heating zone, connect the RTU or

Indoor Sensor to terminals 

Com Sen — RTU 4 (8 and 10).

Common Block for 

RTU 5 and RTU 6

• If the common block is used for a Two Stage heating zone, connect the RTU or

Indoor Sensor to terminals 

Com Sen — RTU 6 (11 and 13).

Output Connections

 

System Pump

Connect the live (L) side of the 120 V (ac) pump circuit through the 

System Pmp —

System Pmp (1 and 2) terminals. The control closes a dry relay contact between these
terminals when operation of the system pump is required.

Zone Pumps and Valves

Note

Do not connect a zone pump and zone valve circuit to the same 

Com terminal.

• If relay 

5 is used, connect the zone pump or zone valve circuit to the Com 5-6 — 5

(25 and 26) terminals on the control.

• If relay 

6 is used, connect the zone pump or zone valve circuit to the Com 5-6 — 6

(25 and 27) terminals on the control.

• If relay 

3 is used, connect the zone pump or zone valve circuit to the Com 3-4 — 3

(22 and 23) terminals on the control.

• If relay 

4 is used, connect the zone pump or zone valve circuit to the Com 3-4 — 4

(22 and 24) terminals on the control.

• If relay 

1 is used for heating (DIP switch set to Zone 1 Heating), connect the zone

pump or zone valve to the 

Com 1-2 — 1 (19 and 20) terminals on the control.

• If relay 

2 is used, connect the zone pump or zone valve circuit to the Com 1-2 — 2

(19 and 21) terminals on the control.

Cooling System

If relay 

1 is used for cooling (DIP switch set to Zone 1 cooling), connect the wires from

the cooling unit isolation relay to terminals 

Com 1-2 —1 (19 and 20) on the control. The

367 closes a dry relay contact between these terminals when cooling is required.

STEP FIVE 

 TESTING THE WIRING 

Each terminal block must be unplugged from its header on the control before power
is applied for testing. Pull straight down to unplug the terminal block.

The following tests are to be performed using standard testing practices and procedures
and should only be carried out by properly trained and experienced persons.

A good quality electrical test meter, capable of reading from at least 0 — 200 V (ac) and at
least 0 — 2,000,000 Ohms, is essential to properly test the wiring and sensors.

Com

Sen

UnO

Sw

5 6

RTU

1

12

RTU

6

11

13

Com

Sen

Com

Sen

14

16

Zo

In

15

17

Zo

Out

RTU

2

7

RTU

3

9

RTU

4

10

8

Com

Sen

Out

Sen

18

RTU

5

Com

Sen

UnO

Sw

5

6

RTU

1

12

RTU

6

11

13

Com

Sen

Com

Sen

14

16

Zo

In

15

17

Zo

Out

RTU

2

7

RTU

3

9

RTU

4

10

8

Com

Sen

Out

Sen

18

RTU

5

Com

Sen

UnO

Sw

5 6

RTU

1

12

RTU

6

11

13

Com

Sen

Com

Sen

14

16

Zo

In

15

17

Zo

Out

RTU

2

7

RTU

3

9

RTU

4

10

8

Com

Sen

Out

Sen

18

RTU

5

19 20 21

1

22

23

3

4

25

5

26

24

Com

5-6

27

Com

1-2

2

Com

3-4

6

19 20 21

1

22 23

3

4

25

5

26

24

Com

5-6

27

Com

1-2

2

Com

3-4

6

19 20 21

1

22 23

3

4

25

5

26

24

Com

5-6

27

Com

1-2

2

Com

3-4

6

19 20 21

1

22 23

3

4

25

5

26

24

Com

5-6

27

Com

1-2

2

Com

3-4

6

3

1 2

N

L

Pmp

4

Power

Pmp

System

12 13 14

16

15

17 18

Com
Sen

UnO

Sw

Out

Sen

RTU

5

RTU

6

Zo

Out

Zo
In

19 20

21

1

22 23

3

4

25

5

26

24

Com

5-6

27

Com

1-2

2

Com

3-4

6

19

20

21

1

22 23

3

4

25

5

26

24

Com

5-6

27

Com

1-2

2

Com

3-4

6

Com

Sen

UnO

Sw

5

6

RTU

1

12

RTU

6

11

13

Com

Sen

Com

Sen

14

16

Zo

In

15

17

Zo

Out

RTU

2

7

RTU

3

9

RTU

4

10

8

Com

Sen

Out

Sen

18

RTU

5

Com

Sen

UnO

Sw

5 6

RTU

1

12

RTU

6

11

13

Com

Sen

Com

Sen

14

16

Zo

In

15

17

Zo

Out

RTU

2

7

RTU

3

9

RTU

4

10

8

Com

Sen

Out

Sen

18

RTU

5

Summary of Contents for Zone Control 367

Page 1: ...ngs pg 9 Technical Data pg 16 Advanced Sequence of Operation pg 10 Limited Warranty pg 16 Advanced Installation pg 12 Zone Control 367 One Two Stage One Stage Floating H1121 2 Made in Canada by tekmar...

Page 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Page 3: ...ontrol must base all Optimum Start Stopcalculationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and...

Page 4: ...agerelay and a Hi stage relay Example An RTU connected between the terminals Com Sen RTU 2 is used to control the output relays 1 and 2 Relay 1 is the Lo stage output relay and relay 2 is the Hi stage...

Page 5: ...re is no RTU or Indoor Sensor connected to terminals Com Sen RTU 1 5 6 the 367 can enable an auxiliary cooling control through output relay 1 Output relay 1 is turned on once the heating zones connect...

Page 6: ...ne valves or pumps If a zone valve or zone pump has not been operated in the past 3 days the 367 turns on the zone relay for 10 seconds Note The zone relay exercising time is increased to 3 minutes if...

Page 7: ...versed UnOccupied Switch Ifanexternaltimerorswitchisused connectthetwowiresfromtheexternaldrycontact switch to the UnO Sw Com Sen 14 and 16 terminals When these terminals short together the control re...

Page 8: ...the control If relay 4 is used connect the zone pump or zone valve circuit to the Com 3 4 4 22 and 24 terminals on the control If relay 1 is used for heating DIP switch set to Zone 1 Heating connect t...

Page 9: ...ction for the zone 1 relay If a zone pump or valve is connected to the terminals Com 3 4 4 22 and 24 follow a similar procedure as described above in the cooling section for the zone 1 relay If a zone...

Page 10: ...as soon as the Occupied period begins If the Optimum Start DIP switch is set to Off the 367 does not start raising the building temperature until the UnOccupied period ends More informa tion on the Op...

Page 11: ...367canoperateafananddampertobringoutsideairintothebuilding for free cooling An Indoor Sensor or RTU must be connected between terminals Com Sen RTU 1 and an Outdoor Sensor must be connected to Com Sen...

Page 12: ...nal on the actuating motor and the output relay 4 terminal 24 is connected to the close terminal on the actuating motor Common Block Com 5 6 If the Com 5 6 common block is used to control a floating a...

Page 13: ...eating zone Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 367 has a test routine which is used to test the main control functions The 367 continually...

Page 14: ...ct between Com 3 4 3 22 and 23 is closed and the device connected to this relay Open should be turned on Zone 4 Hi Stage The relay contact between Com 3 4 4 22 and 24 is closed and the device connecte...

Page 15: ...ctive Outdoor sensor open circuit design out off Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 short circuit RTU 2 short circuit RTU 3 short circuit RTU 4 short circuit...

Page 16: ...ry from state to state or province to province ProductReturnProceduresProductsthatarebelievedtohavedefectsinworkmanship or materials must be returned together with a written description of the defect...

Reviews: