background image

15

STEP NINE 

 BEFORE YOU LEAVE 

• Make sure the wiring safety dividers are installed in their proper locations between compartments with different voltages.

• Install the wiring cover over the wiring chamber and secure it to the base with the two screws provided. Place the front cover on the

control and snap it into place. Install a lock if security is required.

• A sticker has been provided with the control. It is designed to be placed over the Zone 1 ... Zone 6 words

so that the zone names can be written onto the control.

• Place this brochure, and all other brochures relating to the installation, in the protective plastic bag supplied

with the control.

• Place the bag in a conspicuous location near the control for future reference.

• It is important to explain the operation of the control to the end user and to anyone else who may be operating

the system.

Error Messages

Whenever a fault is detected in any of the sensors and / or room temperature units (RTUs), the indicator lights will flash in specific ways,
to indicate the location of the problem. For detailed Sensor and RTU testing instructions see Data Brochures D 070 and D 054.

RTU 4 Temperature sensor missing RTU 5 Temperature sensor missing RTU 6 Temperature sensor missing

Light on continually

Light flashing

Light off

RTU 3 Temperature sensor missing

Zo — in short circuit

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Outdoor sensor open circuit

(design out 

 off)

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

RTU 1 short circuit

RTU 2 short circuit

RTU 3 short circuit

RTU 4 short circuit

RTU 5 short circuit

RTU 6 short circuit

RTU 1 Temperature sensor missing RTU 2 Temperature sensor missing

Outdoor sensor short circuit

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

Internal fault

Power

Heat Required

Occupied

Optimum Start / Stop

UnOccupied

Timer Active

5

Zone 5 / Lo stage /
Open

Zone 6 / Hi stage /
Close

6

4

Zone 4 / Hi stage /
Close

3

Zone 3 / Lo stage /
Open

2

Zone 2 / Hi stage /
Close / Ventilation

Zone 1 / Lo stage /
Open / Cooling

1

Kitchen

Living Room

Bedroo

m 1

Bedroo

m

2

Family

Ro

om

Ba

se

m

en

t

Summary of Contents for Zone Control 367

Page 1: ...ngs pg 9 Technical Data pg 16 Advanced Sequence of Operation pg 10 Limited Warranty pg 16 Advanced Installation pg 12 Zone Control 367 One Two Stage One Stage Floating H1121 2 Made in Canada by tekmar...

Page 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Page 3: ...ontrol must base all Optimum Start Stopcalculationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and...

Page 4: ...agerelay and a Hi stage relay Example An RTU connected between the terminals Com Sen RTU 2 is used to control the output relays 1 and 2 Relay 1 is the Lo stage output relay and relay 2 is the Hi stage...

Page 5: ...re is no RTU or Indoor Sensor connected to terminals Com Sen RTU 1 5 6 the 367 can enable an auxiliary cooling control through output relay 1 Output relay 1 is turned on once the heating zones connect...

Page 6: ...ne valves or pumps If a zone valve or zone pump has not been operated in the past 3 days the 367 turns on the zone relay for 10 seconds Note The zone relay exercising time is increased to 3 minutes if...

Page 7: ...versed UnOccupied Switch Ifanexternaltimerorswitchisused connectthetwowiresfromtheexternaldrycontact switch to the UnO Sw Com Sen 14 and 16 terminals When these terminals short together the control re...

Page 8: ...the control If relay 4 is used connect the zone pump or zone valve circuit to the Com 3 4 4 22 and 24 terminals on the control If relay 1 is used for heating DIP switch set to Zone 1 Heating connect t...

Page 9: ...ction for the zone 1 relay If a zone pump or valve is connected to the terminals Com 3 4 4 22 and 24 follow a similar procedure as described above in the cooling section for the zone 1 relay If a zone...

Page 10: ...as soon as the Occupied period begins If the Optimum Start DIP switch is set to Off the 367 does not start raising the building temperature until the UnOccupied period ends More informa tion on the Op...

Page 11: ...367canoperateafananddampertobringoutsideairintothebuilding for free cooling An Indoor Sensor or RTU must be connected between terminals Com Sen RTU 1 and an Outdoor Sensor must be connected to Com Sen...

Page 12: ...nal on the actuating motor and the output relay 4 terminal 24 is connected to the close terminal on the actuating motor Common Block Com 5 6 If the Com 5 6 common block is used to control a floating a...

Page 13: ...eating zone Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 367 has a test routine which is used to test the main control functions The 367 continually...

Page 14: ...ct between Com 3 4 3 22 and 23 is closed and the device connected to this relay Open should be turned on Zone 4 Hi Stage The relay contact between Com 3 4 4 22 and 24 is closed and the device connecte...

Page 15: ...ctive Outdoor sensor open circuit design out off Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 short circuit RTU 2 short circuit RTU 3 short circuit RTU 4 short circuit...

Page 16: ...ry from state to state or province to province ProductReturnProceduresProductsthatarebelievedtohavedefectsinworkmanship or materials must be returned together with a written description of the defect...

Reviews: