background image

11

Common Blocks    



The 367 has 3 common blocks for both the RTU inputs and relay outputs. Each common block has a terminal starting with 

Com

(e.g. 

Com Sen or Com 1-2 ). When the DIP switch is set to One Stage & Floating, each common block can be used for either two

One Stage zones or one Floating action zone. One Stage common blocks are explained on page 4 of this brochure.

Floating Action Common Blocks  



When the DIP switch is set to 

One Stage & Floating and a single RTU is connected to the highest terminal

number in the common block, a Floating Action zone is created. The single RTU controls two relay outputs
- an 

Open relay and a Close relay. The Motor Speed dial is used to set the time required for the floating action

actuating motor to go from fully closed to fully open.

Example An RTU connected between the terminals 

Com Sen — RTU 2, is used to control the output relays

1 and 2. Relay 1 is the Open relay and relay 2 is the Close relay.

Each floating zone is controlled by repositioning the floating action valve every 15 minutes
based on the space temperature in the zone. The control uses PID logic to maintain an
accurate space temperature. When the measured space temperature is above or below
the desired setpoint, the 367 calculates a new position for the valve and then operates
the 

close or open relay in order to achieve the new position. The floating action output is

designed for either linear modulating injection valves that change the supply water
temperature to the terminal unit or equal percentage modulating valves that change the
flowrate through the terminal unit.

VENTILATION  

The 367 can be used to operate a ventilation system. When the DIP switch on the 367 is
set to 

Zone 2 Ventilating, the 367 ignores the RTU 2 terminal and utilizes the output relay

2 to operate the ventilation system. During the Occupied period, the output relay 2 is turned
on, and during the UnOccupied period the output relay 

2 is turned off. The ventilation system

is therefore only operated during occupied periods in order to conserve energy. If 

Optimum

Start is selected, the 367 starts the ventilation system one hour before the Occupied period
begins. This allows sufficient time to purge the air for normal occupancy.

FREE COOLING  

If the DIP switches are set to both 

Zone 1 Cooling and Zone 2 Ventilating,

the 367 can operate a fan and damper to bring outside air into the building
for free cooling. An Indoor Sensor or RTU must be connected between
terminals 

Com Sen — RTU 1 and an Outdoor Sensor must be connected

to 

Com Sen — Out Sen. Whenever cooling is needed and the heating

zones have been satisfied for at least 45 minutes and the outdoor air
temperature is at least 3

°

F colder than the indoor air temperature, the 367

turns on relays 

1 and 2 together. The 367 varies the on time of output

relays 

1 and 2 over a 30 minute period. As the cooling load increases, the

on time of the output relays increases.

Combining Ventilation, Free Cooling & Mechanical Cooling

All three systems (ventilation, free cooling and mechanical cooling)
can be operated through the appropriate wiring, as shown in the
adjacent diagram. When the 367 is used to operate all three systems,
the output relay 

2 (ventilation) is turned on during occupied periods

whenever cooling is not being done. The 367 operates both output
relay 

1 and output relay 2 (free cooling) when cooling is required and

the outdoor temperature is below the desired indoor temperature.
When the outdoor temperature is warmer than the desired indoor
temperature, the 367 turns off output relay 

2 and turns on output relay

1 in order to run the mechanical cooling system.

DEMAND LIMITING (

Design Outdoor dial)  

The heat supplied to the zones can be limited based on outdoor temperature. Demand Limiting is an energy
saving function that is used to prevent excessive energy consumption when there is an unnecessary heating
load such as an open window during moderate outdoor conditions. This function should only be used if the 367
is not connected to a tekmar reset control. When the 

Design Outdoor dial is turned up from the Off position

and an outdoor sensor is present, the demand limiting function is enabled. Based on the outdoor temperature,
the control restricts the maximum on time of the zone relays. The control allows a full 15 minute on time when
the outdoor temperature reaches the temperature set on the 

Design Outdoor dial. Above this temperature the

maximum on time is reduced until the outdoor temperature reaches the WWSD point where the maximum on
time is zero.

H

C

R

N

C

Floating Zone

Com

1-2

19

1

20

2

21

Com

Sen

5

6

RTU

1

RTU

2

7

Floating Motor

Speed

130 sec.

30

230

100

200

3
4

6

5

7

2
1
8

3
4

6

5

7

2
1
8

M

M

Cool

24 V (ac)

120 V (ac)

N

L

C

R

Zone 1 Cooling

Zone 2 Ventilating

Damper
motor

Fan

2

21

1

20

19

Com

1-2

Zone 2 Ventilating

0

°

F

-40

Off

Design Outdoor

30

Summary of Contents for Zone Control 367

Page 1: ...ngs pg 9 Technical Data pg 16 Advanced Sequence of Operation pg 10 Limited Warranty pg 16 Advanced Installation pg 12 Zone Control 367 One Two Stage One Stage Floating H1121 2 Made in Canada by tekmar...

Page 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Page 3: ...ontrol must base all Optimum Start Stopcalculationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and...

Page 4: ...agerelay and a Hi stage relay Example An RTU connected between the terminals Com Sen RTU 2 is used to control the output relays 1 and 2 Relay 1 is the Lo stage output relay and relay 2 is the Hi stage...

Page 5: ...re is no RTU or Indoor Sensor connected to terminals Com Sen RTU 1 5 6 the 367 can enable an auxiliary cooling control through output relay 1 Output relay 1 is turned on once the heating zones connect...

Page 6: ...ne valves or pumps If a zone valve or zone pump has not been operated in the past 3 days the 367 turns on the zone relay for 10 seconds Note The zone relay exercising time is increased to 3 minutes if...

Page 7: ...versed UnOccupied Switch Ifanexternaltimerorswitchisused connectthetwowiresfromtheexternaldrycontact switch to the UnO Sw Com Sen 14 and 16 terminals When these terminals short together the control re...

Page 8: ...the control If relay 4 is used connect the zone pump or zone valve circuit to the Com 3 4 4 22 and 24 terminals on the control If relay 1 is used for heating DIP switch set to Zone 1 Heating connect t...

Page 9: ...ction for the zone 1 relay If a zone pump or valve is connected to the terminals Com 3 4 4 22 and 24 follow a similar procedure as described above in the cooling section for the zone 1 relay If a zone...

Page 10: ...as soon as the Occupied period begins If the Optimum Start DIP switch is set to Off the 367 does not start raising the building temperature until the UnOccupied period ends More informa tion on the Op...

Page 11: ...367canoperateafananddampertobringoutsideairintothebuilding for free cooling An Indoor Sensor or RTU must be connected between terminals Com Sen RTU 1 and an Outdoor Sensor must be connected to Com Sen...

Page 12: ...nal on the actuating motor and the output relay 4 terminal 24 is connected to the close terminal on the actuating motor Common Block Com 5 6 If the Com 5 6 common block is used to control a floating a...

Page 13: ...eating zone Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 367 has a test routine which is used to test the main control functions The 367 continually...

Page 14: ...ct between Com 3 4 3 22 and 23 is closed and the device connected to this relay Open should be turned on Zone 4 Hi Stage The relay contact between Com 3 4 4 22 and 24 is closed and the device connecte...

Page 15: ...ctive Outdoor sensor open circuit design out off Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 short circuit RTU 2 short circuit RTU 3 short circuit RTU 4 short circuit...

Page 16: ...ry from state to state or province to province ProductReturnProceduresProductsthatarebelievedtohavedefectsinworkmanship or materials must be returned together with a written description of the defect...

Reviews: