background image

14

Step 3  - The control tests relays 3 and 4 using the procedure described in Step 2.

Step 4  - If the DIP switches are set to Zone 1 Heating and Zone 2 Heating, the control tests relays 1 and 2 using the procedure

described in Step 2.

-

If the DIP switch is set to 

Zone 2 Ventilating or its is set to Zone 2 Heating and an RTU is connected to RTU 2, the control

turns on relay 

2 for 10 seconds.

-

If the DIP switch is set to 

Zone 1 Cooling or an RTU is connected to RTU 1 the

control turns on relay 

1 for 10 seconds.

Step 5 - After the test sequence is complete, the Test light begins flashing and the control enters a fast mode of operation. During

this time, the control is more responsive to setting adjustments. If the dial on an RTU is turned up, the on time of the zone
relay increases immediately. After fifteen minutes, the control reverts back to normal operating conditions and the on times
are based on the average temperature during the previous 15 minute cycle.

Manual Test

 

While the control is in the fast mode of operation and the 

Test light is flashing, check that

each RTU operates the proper zone valve or zone pump. Turn up the 

RTU dial to turn the

zone on, turn the dial down to turn the zone off. If an Indoor Sensor is used, a cold spray
to the sensor will turn the zone on.

Indicator Lights “On” 

  

Power

• 120 V (ac) power is applied to the control and the control

is energized.

Heat Required

• The 367 is sending a heat required signal to a tekmar reset control. At least one of the heating zones

requires heat.

System Pump

• The relay contact between 

System Pmp—System Pmp (1 and 2) is closed and the System Pump should

be turned on.

Zone 1 / Lo Stage /

• The relay contact between 

Com 1-2— 1 (19 and 20) is closed and the device connected to this relay

Open / Cooling

should be turned on.

Zone 2 / Hi Stage /

• The relay contact between 

Com 1-2— 2 (19 and 21) is closed and the device connected to this relay

Close / Ventilation

should be turned on.

Zone 3 / Lo Stage /

• The relay contact between 

Com 3-4— 3 (22 and 23) is closed and the device connected to this relay

Open

should be turned on.

Zone 4 / Hi Stage /

• The relay contact between 

Com 3-4— 4 (22 and 24) is closed and the device connected to this relay

Close

should be turned on.

Zone 5 / Lo Stage /

• The relay contact between 

Com 5-6— 5 (25 and 26) is closed and the device connected to this relay

Open

should be turned on.

Zone 6 / Hi Stage /

• The relay contact between 

Com 5-6— 6 (25 and 27) is closed and the device connected to this relay

Close

should be turned on.

Test

• The control is proceeding through the programmed test sequence.

Occupied

• The control is in Occupied mode.

UnOccupied

• The control is in UnOccupied (Night Setback) mode.

Optimum Start / Stop

• The control is warming the building up during the final stages of the UnOccupied period, or the heating

system is turned off during the final stages of the Occupied period.

Timer Active

• The timer is set to enter the UnOccupied mode every 24 hours at the time of day the 

Start button was

pressed.

STEP EIGHT 

 TROUBLESHOOTING 

As in any troubleshooting procedure, it is important to isolate a problem as much as possible before proceeding. The Error Messages
and 

Test button greatly simplify troubleshooting of the 367. When the control is flashing an error message, identify the fault from the

look-up table on page 15 and follow standard testing procedures to confirm the problem. If you suspect a wiring fault, return to steps
three, four and five, and carefully check all external wiring and wiring connections.

Sensor and Internal Faults

 

• If an Outdoor Sensor fault occurs, the 367 operates as if an Outdoor Sensor is not connected. An error message is displayed.

• If an RTU / Indoor Sensor fault occurs or an external Zone Control input 

Zo - in short circuits, the 367 operates as if that RTU or

Zone Control is not connected. An error message is displayed.

• If an internal control fault occurs, the 367 displays an error message. Press the 

Test button to clear the error message. If the error

message remains, the control must be returned for repair.

Adjusting RTU settings provides an immediate

response for the first 15 minutes only.

70

M

Test

Summary of Contents for Zone Control 367

Page 1: ...ngs pg 9 Technical Data pg 16 Advanced Sequence of Operation pg 10 Limited Warranty pg 16 Advanced Installation pg 12 Zone Control 367 One Two Stage One Stage Floating H1121 2 Made in Canada by tekmar...

Page 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Page 3: ...ontrol must base all Optimum Start Stopcalculationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and...

Page 4: ...agerelay and a Hi stage relay Example An RTU connected between the terminals Com Sen RTU 2 is used to control the output relays 1 and 2 Relay 1 is the Lo stage output relay and relay 2 is the Hi stage...

Page 5: ...re is no RTU or Indoor Sensor connected to terminals Com Sen RTU 1 5 6 the 367 can enable an auxiliary cooling control through output relay 1 Output relay 1 is turned on once the heating zones connect...

Page 6: ...ne valves or pumps If a zone valve or zone pump has not been operated in the past 3 days the 367 turns on the zone relay for 10 seconds Note The zone relay exercising time is increased to 3 minutes if...

Page 7: ...versed UnOccupied Switch Ifanexternaltimerorswitchisused connectthetwowiresfromtheexternaldrycontact switch to the UnO Sw Com Sen 14 and 16 terminals When these terminals short together the control re...

Page 8: ...the control If relay 4 is used connect the zone pump or zone valve circuit to the Com 3 4 4 22 and 24 terminals on the control If relay 1 is used for heating DIP switch set to Zone 1 Heating connect t...

Page 9: ...ction for the zone 1 relay If a zone pump or valve is connected to the terminals Com 3 4 4 22 and 24 follow a similar procedure as described above in the cooling section for the zone 1 relay If a zone...

Page 10: ...as soon as the Occupied period begins If the Optimum Start DIP switch is set to Off the 367 does not start raising the building temperature until the UnOccupied period ends More informa tion on the Op...

Page 11: ...367canoperateafananddampertobringoutsideairintothebuilding for free cooling An Indoor Sensor or RTU must be connected between terminals Com Sen RTU 1 and an Outdoor Sensor must be connected to Com Sen...

Page 12: ...nal on the actuating motor and the output relay 4 terminal 24 is connected to the close terminal on the actuating motor Common Block Com 5 6 If the Com 5 6 common block is used to control a floating a...

Page 13: ...eating zone Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 367 has a test routine which is used to test the main control functions The 367 continually...

Page 14: ...ct between Com 3 4 3 22 and 23 is closed and the device connected to this relay Open should be turned on Zone 4 Hi Stage The relay contact between Com 3 4 4 22 and 24 is closed and the device connecte...

Page 15: ...ctive Outdoor sensor open circuit design out off Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 short circuit RTU 2 short circuit RTU 3 short circuit RTU 4 short circuit...

Page 16: ...ry from state to state or province to province ProductReturnProceduresProductsthatarebelievedtohavedefectsinworkmanship or materials must be returned together with a written description of the defect...

Reviews: