background image

9

Test the Sensors

 

In order to test the sensors and Room Temperature Units (RTUs), the actual temperature
at each sensor and RTU location must be measured. A good quality digital thermometer
with a surface temperature probe is recommended for ease of use and accuracy of
testing. Where a digital thermometer is not available, a spare sensor can be strapped
alongside the one to be tested and the readings compared. Test the sensors and RTU(s)
according to the instructions in the Data Brochures D 070 and D 054.

Test the Power Supply

 

Make sure exposed wires or bare terminals are not in contact with other wires or grounded surfaces. Turn on the power and measure
the voltage between the 

Power N — L (3 and 4) terminals using an AC voltmeter. The reading should be between 110 and 130 V (ac).

Test the Outputs

 

System Pump

If a system pump is connected to the 

System Pmp — System Pmp (1 and 2) terminals, make sure power to the terminal block is

off and install a jumper between the terminals. When the system pump circuit is powered up, the system pump should start. If the
pump does not turn on, check the wiring between the terminal block and the pump and refer to any installation or troubleshooting
information supplied with the pump. If the pump operates properly, disconnect the power and remove the jumper.

Cooling

If a cooling system is connected to the terminals 

Com 1-2 —1 (19 and 20), make sure power to the pump or valve circuit is off and

install a jumper between the terminals 

Com 1-2 — 1 (19 and 20). When the zone circuit is powered up, the zone pump should turn

on or the zone valve should open completely. If no response occurs, check the wiring between the terminal and the pump or valve
and refer to any installation or troubleshooting information supplied with these devices.

Zone Pump or Valve

• If a zone pump or valve is connected to the terminals 

Com 5-6 —6 (25 and 27), follow a similar procedure as described above

in the cooling section for the zone 1 relay.

• If a zone pump or valve is connected to the terminals

 Com 5-6 — 5 (25 and 26), follow a similar procedure as described above

in the cooling section for the zone 1 relay.

• If a zone pump or valve is connected to the terminals 

Com 3-4 — 4 (22 and 24), follow a similar procedure as described above

in the cooling section for the zone 1 relay.

• If a zone pump or valve is connected to the terminals 

Com 3-4 — 3 (22 and 23), follow a similar procedure as described above

in the cooling section for the zone 1 relay.

• If a zone pump or valve is connected to the terminals 

Com 1-2 — 2 (19 and 21), follow a similar procedure as described above

in the cooling section for the zone 1 relay.

• If a zone pump or valve is connected to the terminals 

Com 1-2 — 1 (19 and 20), follow a similar procedure as described above

in the cooling section for the zone 1 relay.

Connect the Control

  

• Make sure all power to the devices and terminal blocks is off and remove any remaining jumpers from the terminals.

• Reconnect the terminal blocks to the control by carefully aligning them with their respective headers on the control and then pushing

the terminal blocks into the headers. The terminal blocks should snap firmly into place.

• Install the supplied safety dividers between the unpowered sensor inputs and the powered 120 V (ac) or 24V (ac) wiring chambers.

• Do not apply power to the control until the adjustment dials and DIP switches are properly set for your application. See the Basic

Settings section of this brochure for details on how to set the dials and DIP switches.

• Once the settings are complete, apply power to the control. The operation of the control on power up is described in the Basic

Sequence of Operation section of this brochure.

 

Basic Settings

Before adjusting the dial settings, read through the sequence of operation section of this brochure to ensure that you understand how
the control operates.

STEP SIX 

 ESSENTIAL CONTROL SETTINGS 

Max. Room 

 

The 

Max. Room dial is used to prevent excessive desired indoor temperature settings

during heating operation. If an 

RTU dial is set above the Max. Room dial, the Max. Room

dial becomes the desired indoor temperature. This is useful in situations where a tenant
has control of the RTU but the owner pays the fuel costs.

Design Outdoor 



This dial must be set to the 

Off position unless the Demand Limiting function is used. See

the Advanced section of this brochure for more information.

Max. Room

40

65

°

F

Off

85

0

°

F

-40

Off

Design Outdoor

30

Summary of Contents for Zone Control 367

Page 1: ...ngs pg 9 Technical Data pg 16 Advanced Sequence of Operation pg 10 Limited Warranty pg 16 Advanced Installation pg 12 Zone Control 367 One Two Stage One Stage Floating H1121 2 Made in Canada by tekmar...

Page 2: ...eat can be supplied to the room on the coldest day of the year without requiring that the room be cold Derivative D In order to speed up the control s response to quick changes in the heating load der...

Page 3: ...ontrol must base all Optimum Start Stopcalculationsonindoortemperatureonly Iftherearelargevariationsinoutdoor temperature this method cannot provide the same level of accuracy as when both indoor and...

Page 4: ...agerelay and a Hi stage relay Example An RTU connected between the terminals Com Sen RTU 2 is used to control the output relays 1 and 2 Relay 1 is the Lo stage output relay and relay 2 is the Hi stage...

Page 5: ...re is no RTU or Indoor Sensor connected to terminals Com Sen RTU 1 5 6 the 367 can enable an auxiliary cooling control through output relay 1 Output relay 1 is turned on once the heating zones connect...

Page 6: ...ne valves or pumps If a zone valve or zone pump has not been operated in the past 3 days the 367 turns on the zone relay for 10 seconds Note The zone relay exercising time is increased to 3 minutes if...

Page 7: ...versed UnOccupied Switch Ifanexternaltimerorswitchisused connectthetwowiresfromtheexternaldrycontact switch to the UnO Sw Com Sen 14 and 16 terminals When these terminals short together the control re...

Page 8: ...the control If relay 4 is used connect the zone pump or zone valve circuit to the Com 3 4 4 22 and 24 terminals on the control If relay 1 is used for heating DIP switch set to Zone 1 Heating connect t...

Page 9: ...ction for the zone 1 relay If a zone pump or valve is connected to the terminals Com 3 4 4 22 and 24 follow a similar procedure as described above in the cooling section for the zone 1 relay If a zone...

Page 10: ...as soon as the Occupied period begins If the Optimum Start DIP switch is set to Off the 367 does not start raising the building temperature until the UnOccupied period ends More informa tion on the Op...

Page 11: ...367canoperateafananddampertobringoutsideairintothebuilding for free cooling An Indoor Sensor or RTU must be connected between terminals Com Sen RTU 1 and an Outdoor Sensor must be connected to Com Sen...

Page 12: ...nal on the actuating motor and the output relay 4 terminal 24 is connected to the close terminal on the actuating motor Common Block Com 5 6 If the Com 5 6 common block is used to control a floating a...

Page 13: ...eating zone Testing the Control Functions STEP SEVEN OPERATIONAL TEST OF CONTROL FUNCTIONS The Zone Control 367 has a test routine which is used to test the main control functions The 367 continually...

Page 14: ...ct between Com 3 4 3 22 and 23 is closed and the device connected to this relay Open should be turned on Zone 4 Hi Stage The relay contact between Com 3 4 4 22 and 24 is closed and the device connecte...

Page 15: ...ctive Outdoor sensor open circuit design out off Power Heat Required Occupied Optimum Start Stop UnOccupied Timer Active RTU 1 short circuit RTU 2 short circuit RTU 3 short circuit RTU 4 short circuit...

Page 16: ...ry from state to state or province to province ProductReturnProceduresProductsthatarebelievedtohavedefectsinworkmanship or materials must be returned together with a written description of the defect...

Reviews: