4-37
Group 10 PID Parameters
Code
Parameters
Setting Range
Default Unit
Control Mode
Attribute
V/F
SLV
PM
SLV
10-25 PID Reversal Output Selection
0:No Allowing Reversal Output
1:Allow Reversal Output
0
-
O
O
O
10-26
PID Target Acceleration/
Deceleration Time
0.0~25.5
0.0
s
O
O
O
10-27 PID Feedback Display Bias
-99.99~99.99
0
-
O
O
O
10-28 PID Feedback Display Gain
0.00~100.00
100.00
O
O
O
10-29 PID Sleep Selection
0:Disable
1:Enable
2:Set By DI
1
-
O
O
O
10-30 Upper Limit of PID Target
0.0 ~ 100.0
100.0
%
O
O
O
10-31 Lower Limit of PID Target
0.0 ~ 100.0
0.0
%
O
O
O
10-33 Maximum Value of PID Feedback 1 ~ 10000
999
-
O
O
O
10-34 PID Decimal Width
0 ~ 4
1
O
O
O
10-35 PID Unit
0:%
1:FPM
2:CFM
3:SPI
4:GPH
5:GPM
6:IN
7:FT
8:/s
9:/m
10:/h
11:°F
12:inW
13:HP
14:m/s
15:MPM
16:CMM
17:W
18:KW
19:m
20:°C
21:RPM
22:Bar
23:Pa
0
O
O
O
*7
10-39
* Output Frequency Setting of PID
Disconnection
00.00~599.00
30.00 Hz
O
O
O
10-40
Selection of PID Sleep
Compensation Frequency
0:Disable
1:Enable
0
-
O
O
O
10-47 Proportional Gain (P) of Fire Mode 0.00~10.00
1.00
O
O
O
10-48 Integral Time (I) of Fire Mode
0.00~100.00
1.00
s
O
O
O
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......