4-20
Group 02 IM Motor Parameters
Code
Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F SLV
PM
SLV
02-00 No-Load Current of Motor1 0.01~600.00
KVA
A
O
X
X
02-01 Rated Current of Motor1
Lower limit:
10% Inverter rated current (V/F)
25% Inverter rated current (SLV)
Upper limit:
Based on inverter capacity
KVA
A
O
O
X
02-03
Rated Rotation Speed of
Motor1
0~60000
KVA
RPM O
O
X
*8
02-04 Rated Voltage of Motor1
200V: 50.0~240.0
230.0
V
O
O
X
*8
400V: 100.0~480.0
400.0
02-05 Rated Power of Motor1
0.01~600.00
KVA
kW
O
O
X
02-06 Rated Frequency of Motor1 4.8~599.0
50.0/60.0 Hz
O
O
X
*8
02-07 Poles of Motor 1
2~16(Even)
4
Poles O
O
X
02-09 Excitation Current of Motor 1 15%~70% of motor rated current
KVA
%
X
O
X
02-10 Core Saturation Coefficient 1 1~100
KVA
%
X
O
X
02-11
Core Saturation
Coefficient 2 of Motor 1
1~100
KVA
%
X
O
X
02-12
Core Saturation
Coefficient 3 of Motor 1
80~300
KVA
%
X
O
X
02
-
13 Core loss of Motor 1
0.0~15.0
KVA
%
O
X
X
02-15
Resistance Between Wires of
Motor 1
1~60.000
KVA
Ω
O
O
X
02-16
Rotor Resistance Gain of
Motor 1
1~60.000
KVA
Ω
O
O
X
02-17
Leakage Inductance of
Motor 1
0.001~60.000
KVA
mH
O
O
X
02-19 No-Load Voltage of Motor 1
200V:50~240
400V:100~480
-
V
X
O
X
*8
02-20 No-Load Current of Motor 2 0.01~600.00
KVA
A
O
X
X
02-21 Rated Current of Motor 2
10%~200% of inverter rated current
KVA
A
O
X
X
02-22
Rated Rotation Speed of
Motor 2
0~60000
KVA
RPM O
X
X
*8
02-23 Rated Voltage of Motor 2
200V:50.0~240.0
230.0
V
O
X
X
*8
400V:100.0~480.0
400.0
02-24 Rated Power of Motor 2
0.01~600.00
KVA
kW
O
X
X
02-25 Rated Frequency of Motor 2 4.8~599.0
50.0/60.0 Hz
O
X
X
*8
02-26 Poles of Motor 2
2~16(Even)
4
Poles O
X
X
02-32
Resistance between Wires of
Motor 2
0.001~60.000
KVA
Ω
O
X
X
02-33
Proportion of Motor Leakage
Inductance
0.1~15.0
KVA
%
X
O
X
02-34 Slip Frequency of Motor
0.10~20.00
KVA
Hz
X
O
X
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......