4-125
functions 1 to 6.
The time charts of the frequency agree detection operation are shown in table 4.3.30.
Function
Detection operation of frequency
confirmation
Description
Frequency
agree
time
time
ON
OFF
FWD
REV
03-14
03-14
Freq
Reference
Output
Frequency
Frequency
Agree
Signal
ON
Freq
Reference
Output is active when the output
frequency falls within the frequency
reference minus the frequency
detection width (03-14).
Any of the digital outputs function
(03-11, 03-12 or 03-28) can be set to
2
(Frequency agree).
Set
frequency
agree
time
time
ON
OFF
FWD
REV
03-14
Output
Frequency
Setting
Frequency
Agree
Signal
ON
03-13
03-13
03-14
Output is active the output frequency
falls within the frequency detection
width (03-14) of the set frequency
detection level (03-13).
Any of the digital outputs function
(03-11, 03-12 or 03-28) can be set to 3
(Set frequency agree).
Output
frequency
detection
1
ON
ON
OFF
OFF
03-14
03-14
03-13
03-13
03-13
03-13
time
time
Output
Frequency
Output
Frequency
Detection 1
Signal
Output is active when the output
frequency rises above the frequency
detection level (03-13) + frequency
detection width (o3-14) and
deactivates when the output
frequency falls below frequency
detection level (03-13).
Any of the digital outputs function
(03-11, 03-12 or 03-28) can be set to 4
(Output frequency detection 1).
Output
frequency
detection
2
Output is active when the output
frequency is below the frequency
detection level (03-13) + frequency
detection width (03-14) and turns off
when the output frequency rises above
below frequency detection level.
Any of the digital outputs function
(03-11, 03-12 or 03-28) can be set to 5
(Output frequency detection 2).
Frequency
Output
DC Brake
DC Brake
ON
ON
OFF
OFF
Output
Frequency
Frequency
Output
Ing
OFF
OFF
OFF
OFF
OFF
ON
ON
Run
command
Base
Block
When the inverter output frequency is
active, the output terminal is closed.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......