13-08=6:2 wires initialization (230V/400V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2)
Inverter input voltage (01-14) is automatically set to 230V (220V calss) or 400V (440V calss).
(3)
When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=7:2 wires initialization (220V/440V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2)
Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 440V(440V calss).
(3)
When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=8:2 wires initialization (220V/440V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2)
Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 440V(440V calss).
(3)
When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=9:2 wires initialization (220V/380V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2)
Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 380V(440V calss).
(3)
When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=10:2 wires initialization (220V/380V)
(1)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2
controls reverse operation / stop command. Refer to figure 4.3.1.
(2)
Inverter input voltage (01-14) is automatically set to 220V(220V calss) or 380V(440V calss).
(3)
When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=1112:PLC initialization
Clear built-in PLC ladder logic and related values.
The following parameters will not be influenced by restore factory setting (13-08)
No.
Parameters
00-00
Control Mode Selection
00-34
Language selection
00-27
HD/ND Mode Selection
01-00
V/F Curve Selection
01-26
V/F Curve Selection of Motor 2
13-00
Inverter Capacity Selection
13-03
Cumulative Operation Hours 1
13-04
Cumulative Operation Hours 2
13-05
Selection of Cumulative Operation Time
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......