168
08 – 56
Detection Level of Fire Mode AI2 Signal
Range
【0~100】%
08 - 57
Delay Time of Fire Mode AI2 Signal Loss
Range
【0.0~10.0】Sec
08 - 58
Selection of Fire Mode AI2 Signal Loss
Range
【0】:Keep Running
【1】:Fire Mode Speed(08-52)
【2】:Max. Output Frequency of Motor 1 (01-02)
When 08-51=2 (AI2), inverter will trigger AI2 feedback loss detection function automatically.
Selection of Fire Mode AI2 Signal Loss (08-58) :
When 08-51=0, output frequency will be fixed on current frequency.
When 08-51=1, output frequency will be based on the setting value of parameter 08-52.
When 08-51=2, output frequency will be based on the setting value of parameter 01-02.
If AI2 signal is less than the setting value of 08-56 in 360ms, and the time longer than setting value
of 08-57, the frequency reference will be considered to loss.
Analog signal will compare with the previous value at 360ms, if inverter ensure the frequency
reference already loss, frequency reference will base on the value of 08-58.
Fig 4.3.76 AI2 frequency reference loss
08 - 59
Fire Mode Motor Direction
Range
【0】: Forward
【1】: Reverse
When fire mode is enabled, motor direction will base on the setting of 08-59.
08 - 60
Fire Mode Password
Range
【00000 ~ 65534】
When fire mode is enabled, use can set password in parameter 08-60, please refer the
process of parameter 13-07.
In order to prevent the parameters of fire mode being modified, keypad display will just
show the related parameters of fire mode when fire mode is enabled. (Parameter
08-48~08-60 will be read only).
Parameter 08-60(password of fire mode) and 13-07(parameter password), only one
parameter can be allowed to set at the same time.
Summary of Contents for E510-201-SH
Page 1: ......
Page 28: ...3 14 b 200V 2HP 1 3PH 200V 3HP 20HP 400V 3HP 25HP IP20 NEMA1 ...
Page 29: ...3 15 c 200V 25HP 400V 30HP d 200V 30HP 40HP 400V 40HP 75HP ...
Page 51: ...3 37 3 5 Standard Wiring 10V AI1 AI2 AGND E P P ...
Page 72: ...4 6 4 1 4 Example of keypad operation Example 1 Modifying parameters ...
Page 74: ...4 8 4 1 5 Operation control ...
Page 206: ...4 140 Acceleration Deceleration calculation of mode 2 ...
Page 316: ...4 250 6 Timer mode 6 FLASH Timer mode 2 7 Timer mode 7 FLASH Timer mode 3 ...
Page 424: ...REVISIONS Date Manual Number Revision May 2017 4KA72X645T01 First edition ...
Page 425: ......