FIG. 19 

 

safety clamps 

 
 
4.5.3 

Transmission 

 
Before starting the air-conditioning unit please check: 

-

 

the tension of the V-belts (section 5.2.3.1) 

-

 

that the pulleys are aligned (section 5.2.3.1) 

-

 

that  the  dowels,  shown  in  fig.  20,  in  their  possible 
installation  positions,  are  doing  their  function  of 
securing the pulleys to the hubs 

 

 

 
4.6 

FAN-MOTOR UNITS (1-PHASES) series TS, PA, TA 

 
4.6.1

 

Electric motors 

 

 
Before starting up the unit: 

-

 

inspect the motor CONTROL BOARD and check that 
the  motor  protection  devices  are  sized  for  the 
maximum  amperage,  corresponding  to  the  rated 
value on the plate. 

-

 

The  thermal  protections,  if  present,  must  not  be 
connected  to  the  power  supply  line  of  the  electric 
motors  since  otherwise  they  would  be  damaged 
irreparably 

-

 

Check that the MAINS SUPPLY VOLTAGE is suited to 
that  of  the  motors  as  indicated  on  the  relevant 
plates 

 

4.6.1.1

 

3-speed fans series TS and PA 

 
The scheme on fig. 21 shows the ‘code colour’ of the terminal 
plate installed on the fans used for the 

TS

 and 

PA

 series. 

 
 
FIG. 21 

WHITE 

-------------  COMMON 

RED 

-------------  LOW SPEED 

BLUE 

-------------  MEDIUM SPEED 

BLACK 

-------------  HIGH SPEED 

fa

n

 m

o

to

STRIPED  ___ 

 

 

 

     I 

 

 

 

     I 

 

 

 

     I 

 

 

 

PE 

 

 
The  scheme  on  fig.  22  shows  the  connection  of  a  fan  motor 
actuated by the 3-speed selector  type ‘6990’. 
 
 
FIG.22 

WHITE 

------------------------------- 

RED 

------------------------------- 

BLUE 

------------------------------- 

BLACK 

------------------------------- 

fa

n

 m

o

to

STRIPED  ___       ___________ 

 

 

     I       I 

       _____ 

c

o

m

m

u

te

 

 

     I       I 

       I 

 

 

 

 

     I       I 

       I 

 

 

 

 

PE 

 

 

 
 
4.6.1.2

 

Self-regulating fans series TA 

 
The  ECM2  fans  are  supplied  in  3  parts:  the  fan-motor 
assembly  with  power  box  (fig.  23)  installed  and  wired,  the 
control cable with connector RJ45, the control box. 
 
The power circuit ECM2 is designed to be supplied at 230V – 
50Hz. 
 
FIG.23 

 

 
 

Summary of Contents for T Series

Page 1: ...INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL AIR CONDITIONING UNITS SERIES T TS TA PA...

Page 2: ...ion and protection 7 accessories 4 5 2 Fan 7 4 5 3 Transmission 8 4 6 FAN MOTOR UNITS 1 PHASES series TA PA TA 8 4 6 1 Electric motors 8 4 6 1 1 3 speed fans series TS and PA 8 4 6 1 2 Self regulating...

Page 3: ...e various safety rules in force Integrity of all the system s component parts Application of the identification operation and safety notices On completion of the inspection the Chief Inspector applies...

Page 4: ...t the hydraulic connections are protected by the relevant caps as they were delivered by TCF If they are not plug them in order to protect them exchangers 3 3 POSITIONING 3 3 1 Dimensions of installat...

Page 5: ...o enhance the seal If the connection is made with rubber canvas joints make sure they are not tightened on assembly completion so as to prevent damage or the transmission of vibrations In order to ens...

Page 6: ...may be provided fig 10 This configuration must be determined at the design stage and not during installation since on obvious reduction in efficiency will result if a heat exchanger sized for reverse...

Page 7: ...motors Before starting up the unit inspect the motor CONTROL BOARD and check that the motor protection devices are sized for the maximum amperage corresponding to the rated value on the plate The TERM...

Page 8: ...AHLANDER commutable winding fig 18 offer the advantage of generating greater power than motors of the same size but with separate windings 4 5 1 4 Permitted start up time Because of the temperature in...

Page 9: ...e connected to the power supply line of the electric motors since otherwise they would be damaged irreparably Check that the MAINS SUPPLY VOLTAGE is suited to that of the motors as indicated on the re...

Page 10: ...e initial operating point of the system i e with clean filters To elaborate the built in alarm you nee to memorize this pressure with the microprocessor Memorizing procedure see attachment 2 page 18 A...

Page 11: ...phragm as long as possible the condition of the prefilters must be carefully monitored Moreover TCF recommends to check the state of the gaskets of the frame and the springs every week to prevent air...

Page 12: ...ject to the environmental conditions and the maximum temperature range during operation TABLE 3 Lubrication of fan support bearings 5 4 2 Motor In order to maintain the motor in perfect working order...

Page 13: ...mber of belts must always match the number of races in this type of drive system the belt slack must be on the same side as shown in fig 29 before they are tightened FIG 29 5 5 TROUBLESHOOTING The mos...

Page 14: ...anger connected with moving parts and warning him to disconnect the system power before opening the inspection doors fig 30 FIG 30 6 3 PRACTICAL ACCIDENT PREVENTION TIPS Open the inspection doors only...

Page 15: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 14 8 ATTACHMENT 1...

Page 16: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 15...

Page 17: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 16 9 ATTACHMENT 2...

Page 18: ...control box In order to prevent all interferences we recommend to separate the cable of all the external sources of disturbance Use one of the cables of the following list or equivalent 2 Connecting...

Page 19: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 18...

Reviews: