background image

 

 

TCF Termoventilatori Condizionatori Felsinea  Srl 

40057 Cadriano di Granarolo Emilia (Bologna), via Giuseppe di Vittorio 5 

www.tcf.it 

In  order  to  prevent  overflowing  from  the  condensate 
collection  tank  and  consequent  flooding  of  the  machine  and 
the  room  it  is  installed  in,  the  siphon  must  be  fitted  with  a 
DRAIN VALVE to permit the removal of impurities which may 
deposit on the bottom (fig. 13). 
 
FIG. 13 

 

 
In  order  not  to  undermine  the  operation  of  the  drainage 
system,  pressurised  siphons  and  siphons  operating  under 
suction pressure must not be connected together. 
 
The WASTE PIPE (fig. 14) leading to the drainage network: 

-

 

must  not  be  connected  directly  to  the  siphon  in 
order to absorb air or waste backflow and to permit 
direct visual control of the correct outflow of waste 
water 

-

 

must have a diameter larger than the drain pipe and 
a  minimum  angle  of  2%  to  ensure  proper 
functioning. 

 
FIG. 14 

 

 
4.4

 

FILTRATING SECTIONS 

 
Check  the  correct  installation  of  the  prefilters  located  in  the 
relevant counterframes with safety springs or guides. 
 
 
 
 
 

4.5

 

FAN-MOTOR UNITS (3-PHASES) series T 

 

 
4.5.1

 

Electric motors 

 
Before starting up the unit: 

-

 

inspect the motor CONTROL BOARD and check that 
the  motor  protection  devices  are  sized  for  the 
maximum  amperage,  corresponding  to  the  rated 
value on the plate. 

-

 

The TERMISTORS, if present, must not be connected 
to the power supply line of the electric motors since 
otherwise  they  would  be  damaged  irreparably 
(operating voltage 1V) 

-

 

Check that the MAINS SUPPLY VOLTAGE is suited to 
that  of  the  motors  as  indicated  on  the  relevant 
plates 

 
4.5.1.1

 

Connection for direct starting 

 
The  simplest  electric  motor  start-up  system  is  obtained  by 
connecting  the  motor  directly  to  the  supply  line.  However, 
this  method  has  limitations  due  to  the  high  start-up  current 
(pick-up);  this  type  of  start-up  is  recommended  for  power 
ratings  up  to  5,5kW  for  which  TCF  installs,  as  standard,  4-
poles 220/380 V three-phase motors.  
The wiring diagrams are shown in fig. 15. 
 
FIG. 15 

 

 
4.5.1.2

 

Connection with star-delta starting 

 
If the motor start-up current exceeds the value permitted by 
the  power  supply,  you  may  decide  to  choose  for  delta-star 
starting. 
For  this  purpose  TCF  installs  dual  voltage  400/690V  motors 
on its air-conditioning units starting from an output of 7,5kW, 
thus  allowing  the  motor  to  operate  normally  at  400V  (delta 
connection) and to start-up at 690V (star connection). 
 
 
 

Summary of Contents for T Series

Page 1: ...INSTRUCTIONS OPERATION AND MAINTENANCE MANUAL AIR CONDITIONING UNITS SERIES T TS TA PA...

Page 2: ...ion and protection 7 accessories 4 5 2 Fan 7 4 5 3 Transmission 8 4 6 FAN MOTOR UNITS 1 PHASES series TA PA TA 8 4 6 1 Electric motors 8 4 6 1 1 3 speed fans series TS and PA 8 4 6 1 2 Self regulating...

Page 3: ...e various safety rules in force Integrity of all the system s component parts Application of the identification operation and safety notices On completion of the inspection the Chief Inspector applies...

Page 4: ...t the hydraulic connections are protected by the relevant caps as they were delivered by TCF If they are not plug them in order to protect them exchangers 3 3 POSITIONING 3 3 1 Dimensions of installat...

Page 5: ...o enhance the seal If the connection is made with rubber canvas joints make sure they are not tightened on assembly completion so as to prevent damage or the transmission of vibrations In order to ens...

Page 6: ...may be provided fig 10 This configuration must be determined at the design stage and not during installation since on obvious reduction in efficiency will result if a heat exchanger sized for reverse...

Page 7: ...motors Before starting up the unit inspect the motor CONTROL BOARD and check that the motor protection devices are sized for the maximum amperage corresponding to the rated value on the plate The TERM...

Page 8: ...AHLANDER commutable winding fig 18 offer the advantage of generating greater power than motors of the same size but with separate windings 4 5 1 4 Permitted start up time Because of the temperature in...

Page 9: ...e connected to the power supply line of the electric motors since otherwise they would be damaged irreparably Check that the MAINS SUPPLY VOLTAGE is suited to that of the motors as indicated on the re...

Page 10: ...e initial operating point of the system i e with clean filters To elaborate the built in alarm you nee to memorize this pressure with the microprocessor Memorizing procedure see attachment 2 page 18 A...

Page 11: ...phragm as long as possible the condition of the prefilters must be carefully monitored Moreover TCF recommends to check the state of the gaskets of the frame and the springs every week to prevent air...

Page 12: ...ject to the environmental conditions and the maximum temperature range during operation TABLE 3 Lubrication of fan support bearings 5 4 2 Motor In order to maintain the motor in perfect working order...

Page 13: ...mber of belts must always match the number of races in this type of drive system the belt slack must be on the same side as shown in fig 29 before they are tightened FIG 29 5 5 TROUBLESHOOTING The mos...

Page 14: ...anger connected with moving parts and warning him to disconnect the system power before opening the inspection doors fig 30 FIG 30 6 3 PRACTICAL ACCIDENT PREVENTION TIPS Open the inspection doors only...

Page 15: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 14 8 ATTACHMENT 1...

Page 16: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 15...

Page 17: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 16 9 ATTACHMENT 2...

Page 18: ...control box In order to prevent all interferences we recommend to separate the cable of all the external sources of disturbance Use one of the cables of the following list or equivalent 2 Connecting...

Page 19: ...TCF Termoventilatori Condizionatori Felsinea Srl 40057 Cadriano di Granarolo Emilia Bologna via Giuseppe di Vittorio 5 www tcf it 18...

Reviews: