9. SERVICING (CAREL)
9.1. COMPRESSOR AND UNIT HOUR-METER CONTROL
9.2. INPUTS/OUTPUTS TEST
At any time, it is possible to check the number of compressors running hours for unit maintenance.
When the hour-meter of the individual device reaches the set alarm threshold (Maintenance menu), the
maintenance alarm related to the relevant device is activated. The maintenance alarm is a warning-only
alarm.
All the inputs and outputs can be checked in the Inputs/Outputs menu. To see the inputs exactly as they are
read by the controller without any setting or conversion, look at the Maintenance menu.
Moreover, it is possible to activate manually all the analogue and the digital outputs, when the unit is
switched OFF, via the Maintenance menu.
Be careful : When operating manually the digital outputs, the basic protections are still active and the
relevant alarms are still displayed and stored but the devices will stay ON unless the unit is switched ON. In
that case, all the manual outputs are reseted to avoid mistakes when the unit is switched OFF again.