English
Room Temp.
Winter
Setpoint
Comp_Diff
Gas_Diff
Gas_Offset
compressor
operation
Stage 2
Stage 1
1/2
1/2
Supply air
temperature
Gas Supply
Setpoint
Gas_Supply_Diff
Activatable
deactivated
Activatable
deactivated
Gas stage 1
Gas stage 2
20 SysAer
3.11.4. GAS BURNER TWO STAGE
In Winter mode, two contacts control the gas burner stages as shown in the following diagram:
Maximum Supply Air Temperature limitation
If the supplied air is too high, this function can limit activation of one or both the burner stages as the figure
below:
The supply setpoint is set to 65°C and the differential to 10°C.