English
37
SysAer
* with delay from compressors start-up
Manual : The alarm is displayed until a manual reset but the function(s) linked to the alarm automatically
restart if the alarm cause is not present any more.
Automatic: The alarm is displayed while the alarm is active and automatically disappears
Code
Alarm description
Action
Reset
Delay
Notes
AL26
B7 sensor fail
- OAT
- CST 1
/
Circuit 1 OFF
Manual
60 s
Stops the
functions
Needed for EEV1
AL27
B8 sensor fail
- OAT
- CST 2
/
Circuit 2 OFF
Manual
60 s
Stops the
functions
Needed for EEV2
AL28
Electrical Heater thermal lockout
Heater 1 OFF
Manual
No
View only
AL30
Smoke detector
General OFF, parametrable
actions on Economizer and
extractor fan
Automatic
No
AL31
Circuit 1 High pressure cutout
Circuit 1 OFF
Automatic
No
AL32
Circuit 2 High pressure cutout
Circuit 2 OFF
Automatic
No
AL33
Circuit 1 Low pressure cutout
Circuit 1 OFF
Automatic
Yes, fixed*
AL34
Circuit 2 Low pressure cutout
Circuit 2 OFF
Automatic
Yes, fixed*
AL35
PLAN network failure (on the Master unit) /
AL36
PLAN network failure (on each Slave unit) /
Manual
Yes, fixed
AL37…AL66
General alarm of each Plan unit
/
Automatic
No
View only
AL67
B1 sensor fail (I/O expansion RAH OR IAQ) /
Manual
60 s
Stops the
functions
AL68
B2 sensor fail (I/O expansion IAH)
/
Manual
60 s
Stops the
functions
AL69
B3 sensor fail (I/O expansion OAT)
/
Manual
60 s
Stops the
functions
AL70
B4 sensor fail (I/O expansion SAT)
/
Manual
60 s
Stops the
functions
AL71
MI/O expansion communication failure
/
Manual
30 s
Stops the
functions
AL72
Main blower thermostat lockout
Gas burner OFF
Manual
No
AL73
Main blower thermostat cutout
Gas burner OFF
Automatic
No
AL74
Gas burner internal board alarm
Gas burner OFF
Manual
No
Display and board
reset
AL75
Return blower thermal lockout
General OFF
Manual
No
AL78
Circuit 1 de-frosting frequency alarm too
high
Manual
No
AL79
Circuit 1 de-frosting frequency warning
too high
Automatic
No
AL80
Circuit 1 de-frosting time alarm too long
De-frosting off
Manual
No
AL81
Circuit 2 de-frosting frequency alarm too
high
Manual
No
AL82
Circuit 2 de-frosting frequency warning
too high
Automatic
No
AL83
Circuit 2 de-frosting time alarm too long
De-frosting off
Manual
No
AL84
Thermodynamic recovery alarm
Thermo recovery off
Automatic
No
Refer to the
thermo. recov.
screen