English
8 SysAer
3.2.2. REMOTE ON/OFF
3.2.3. ON/OFF BASED ON TIMER CLOCK
3.2.4. ON/OFF BY SUPERVISOR (OR BMS : B
UILDING
M
ANAGEMENT
S
YSTEM
)
3.2.5. ON/OFF BY PLAN NETWORK
The unit is ON if the following conditions are encountered:
²
If the digital input ID5 is active via the Service menu
²
If the dry contact is closed
The unit is OFF if the contact is open.
The unit is ON if all the following conditions are encountered:
If the unit has a clock card fitted
²
If the clock card is active via the Service menu
²
If the daily scheduling is active via the Clock menu
²
If the daily scheduling is configured in ON/OFF (not in Unoccupied)
²
If the hour is inside the programmed time band
²
If the weekly scheduling is active and the current day is programmed ON
The unit is OFF if the hour is outside the band or the current day is programmed OFF.
The unit is ON if all the following conditions are encountered:
²
If the unit is connected to a supervisor
²
If ON/OFF by supervisor is active via the Service menu
²
If the communication parameters are configured via the Service menu
²
If the supervisor sends ON
The unit is OFF is the supervisor sends OFF.
The unit is ON if all the following conditions are encountered:
²
If the unit is connected to a Master unit in Plan
²
If the unit is configured as Slave
²
If the Master unit is ON
The (Slave) unit is OFF if the Master unit is OFF.
3.2.1. KEYING ON/OFF:
Select UNIT ON/OFF from the main menu and press ENTER: pressing the ENTER key on the display, you
switch the unit ON and OFF. If the unit is switched OFF via the display, none of the other ON/OFF procedures
can be used to switch it back ON. If the unit is OFF, all unit functions and its various controls are disabled,
except smoke detection.