Code
Alarm description
Action
Reset
Delay
Notes
AL01
Compressor(s) / condensing fan(s) circuit
1 thermal lockout
Circuit 1 OFF
Manual
No
AL02
Compressor(s) / condensing fan(s) circuit
2 thermal lockout
Circuit 2 OFF
Manual
No
AL03
Circuit 1 High Pressure lockout
Circuit 1 OFF
Manual
No
AL04
Circuit 2 High Pressure lockout
Circuit 2 OFF
Manual
No
AL05
Hot water coil antifreeze alarm
Close the Economizer,
open the hot water valve Manual
No
AL06
High room temperature
/
Manual
Settable
View only
AL07
Low room temperature
/
Manual
Settable
View only
AL08
Circuit 1 Low Pressure lockout
Circuit 1 OFF
Manual
No
AL09
Circuit 2 Low Pressure lockout
Circuit 2 OFF
Manual
No
AL10
Compressor 1 circuit 1 maintenance
/
Manual
Settable
View only
AL11
Compressor 1 circuit 2 maintenance
/
Manual
Settable
View only
AL12
Compressor 2 circuit 1 maintenance
/
Manual
Settable
View only
AL13
Compressor 2 circuit 2 maintenance
/
Manual
Settable
View only
AL14
Unit maintenance
/
Manual
Settable
View only
AL15
Main fan thermal lockout
General OFF
Manual
No
AL16
Dirty filter
/
Manual
Settable
View only
AL17
Summer Set point < Winter Set point - 2
Auto changeover OFF
Manual
No
AL18
Air Flow-switch
General OFF
Manual
Settable
AL19
Clock broken or no clock
/
Manual
No
View only
AL20
B1 sensor fail
- RAH or IAQ
- EP 1
/
Circuit 1 OFF
Manual
60 s
Stops the
functions
Needed for EEV1
AL21
B2 sensor fail
- OAH
- EP 2
/
Circuit 2 OFF
Manual
60 s
Stops the
functions
Needed for EEV2
AL22
B3 sensor fail (OCT 1)
Circuit 1 OFF in winter
mode
Manual
60 s
Stops the
functions
AL23
B4 sensor fail (OCT 2)
Circuit 2 OFF in winter
mode
Manual
60 s
Stops the
functions
AL24
B5 sensor fail (Smoke detector converted
in digital input)
/
Manual
60 s
Stops the
functions
AL25
B6 sensor fail (RAT)
General OFF
Manual
60 s
8. ALARM MANAGEMENT
When an Alarm is triggered, action is taken on devices, where this option is provided for, and the LED, remote
relay and relevant screens are all activated at the same time.
To view the alarm triggered, simply press the Alarm key - you can then use the UP/DOWN keys to scroll
through the list and view other alarms that might have been triggered. To reset Alarms in the log, you must
call up the alarm screens and press the ALARM key again.
An alarm history is always available where the 150 last alarms are stored. It is possible to reset this history
via the maintenance menu. When the clock board is present, the hour and date of appearance of each alarm
are also stored.
8.1. MAIN CONTROLLER ALARMS (CAREL)