Harmonics current
Active power factor adjustment for sinusoidal input current (PFC = Power Factor
controller), harmonic current in accordance with EN 61000-3-2 are guaranteed
Vibratory strength
(for vertical installation, i.e. cable inlet
down).
Broadband noise (simulated life-endurance test) in accordance with EN 61373,
category 1 class B.
Shock test according to EN 61373, category 1
Housing protection
IP54
*
Regarding the mains connection, these devices are to be classi
fi
ed as category
“
C2
”
devices according to the relevant
DIN EN 61800-3. The increased requirements placed on electrical interference > 2 kHz for category
“
C1
”
devices are
complied with in addition.
8.1.1
Max. load dependent on ambient temperature and line voltage.
The maximum permissible temperature for the rated current at rated voltage is speci
fi
ed as rated
temperature.
Since the dissipation of the power loss (heat development) in the device is decisively dependent on
the ambient temperature, the max. load must be reduced at an ambient temperature above the rated
temperature (
following table)!
The average value measured during a 24 h period must be 5 K under the max. ambient temperature.
For installation in a switch cabinet, the device
’
s dissipation and its possible affect on the ambient
temperature must be taken into consideration!
Type
Maximal motor current depending on ambient temperature
@ 40
°
C
[A]
@ 45
°
C
[A]
@ 50
°
C
[A]
@ 55
°
C
[A]
FRQ(5)-E-6A
6.0
5.5
4.5
4.0
FRQ(5)-E-10A
10.0
10.0
10.0
9.0
Operating Instructions
FRQ5S-E-6/10A
Enclosure
L-BAL-E247-GB 1512 Index 001
Part.-No. 00163444-42
15/17