Code

Relay 

K2

Explanation 

Reaction of Controller

Adjustment

7

de-energized
terminals 21 - 22 bridged

Earth fault

Shortcut between one motor wire and PE

The unit cuts out and does not switch on 
again.
Disconnect the device from mains.
Check motor wires

A permanent shortcut earth can dam-
age the device!

8

-

Overvoltage

DC overvoltage because of shortcut earth 
at switch-on.

The unit cuts out.
Disconnect the device from mains.
Check motor wires

8

Enclosure

8.1

Technical data

Type

FRQ5S-E-6A

FRQ5S-E-10A

Part-No.

37421

(308307-42)

37422

(308308-42)

Rated current output {1}

6 A

10 A

Rated current input {2}

6.3 A

10.8 A

Max. load limit integral of cut-in current {2}

0,7

1,3

Max. line fuse {3} 

10 A

16 A

Max. leakage current according to the dened networks of 
DIN EN 60990 (depending on connected line voltage *)  

2.6 mA (U

typ

 230 V) 

3.5 mA (U

max

 305 V) 

3.0 mA (U

type

 230 V) 

4.0 mA (U

max

 305 V) 

Max. heat dissipation approx. {2} 

103 W

187 W

Rated temperature

40 

°

C

50 

°

C

Weight

5.7

6.7 kg

{1}

Rated current output 

 

current indication rating plate @ rated voltage, @ rated temperature (cos 

φ

 0.8 at the output) 

{2}

At rated voltage (cos 

φ

 0.8 at the output), values for different speci

cations on request.

{3}

Max. supply side line fuse according to DIN EN 60204-1 classi

cation VDE0113 chapter 1  

Line voltage*

1 ~ 208...277 V (-10...+10 %), 50/60 Hz

Rated voltage

230 V

Maximal output voltage

1 ~ 230 V
The PFC (Power Factor Controller) makes it mostly independent of the mains 
voltage

Maximal output frequency 

50 Hz

Edgefrequency

50 Hz

U/f-characteristic curve

linear

Switching frequency

16  kHz

Rampup time 

20 sec

Rampdown time

20 sec

Power factor 

> 0.9

Heat dissipation in standby operation

approx. 2.6 W

Max. contact rating of the internal relay

2 A / 250 VAC

Max. permissible ambient temperature 

55 

°

C

Min. permissible ambient temperature

°

C (if mains voltage is not switched off up to -20 

°

C)

Max. permissible installation height 

0...4000 m amsl
above 1000 m amsl the rated current is to be reduced by 5 % / 1000 m

Permissible rel. humidity

85 % no condensation

Electromagnetic compatibility for the 
standard voltage  230 / 400 V according 
to DIN IEC 60038

Interference emission EN 61000-6-3 (domestic household applications)

Interference immunity EN 61000-6-2 (industrial applications)

Operating Instructions 

FRQ5S-E-6/10A

Enclosure

L-BAL-E247-GB 1512 Index 001

Part.-No. 00163444-42

14/17

Summary of Contents for FRQ5S-E-10A

Page 1: ...with sine lter for 1 fans Operating Instructions Speed controller with 5 step switch for presetting the fan speed Keep for reference Software version D1628A from Version 11 03 L BAL E247 GB 1512 Index...

Page 2: ...tdoor installation 8 4 4 Installation location for agriculture 9 4 5 Temperature in uences during commissioning 9 5 Electrical installation 9 5 1 Safety precautions 9 5 2 EMC compatible installation 9...

Page 3: ...ical data 14 8 1 1 Max load dependent on ambient temperature and line voltage 15 8 2 Connection diagram 16 8 3 Dimensions mm 16 8 4 Manufacturer reference 17 Operating Instructions FRQ5S E 6 10A L BAL...

Page 4: ...consequence of unauthorized repairs or modi cations 1 4 Copyright These operating instructions contain copyright protected information The operating instructions may be neither completely nor partiall...

Page 5: ...directives rules for the prevention of accidents and the corresponding national as well as regional and in house regulations Personnel to be trained or instructed and apprentices are only permitted to...

Page 6: ...ufacturer s original spare parts wearing parts accessories These parts are specially designed for this device If parts from other sources are used there is no guarantee that they are designed and prod...

Page 7: ...tep 5 to step 0 is not possible 0 1 2 3 4 5 0 Hz 10 Hz 20 Hz 30 Hz 40 Hz 50 Hz 23 05 2013 v_5_step_icontr_basic_sa vsd The output frequency can be adapted by an internal potentiometer if necessary inv...

Page 8: ...an be easily accessed Depending on the housing model cut off necessary cable inlets respectively to the cable diameter Or alternative use cable inlet for cable glands Metal sheet housings are supplied...

Page 9: ...the device Disregarding this regulation can lead to severe personal injury For metal cable inlets the necessary protective earth connection to the bottom of the housing is made by screws The device ma...

Page 10: ...between two outer conductors all current sensitive fault current circuit breakers must be used EN 50 178 Art 5 2 5 5 Inverter output 5 5 1 Motor connection The motor leads are connected to the termin...

Page 11: ...at certain frequencies Potemtiometer adjustable with a screwdriver Left stop No reduction i e output frequency e g in step 5 50 Hz factory setting diagram Right stop Maximum reduction 25 i e output fr...

Page 12: ...tion below 3 Hz switch off by the enable switch off of line voltage or in case of a fault the relay de energizes 5 9 Bypass circuit Please observe the following during bypass switching controller shun...

Page 13: ...tion above 5 Hz terminals 21 24 bridged De energized at modula tion below 3 Hz 21 22 bridged Temperature management active The device has an active temperature management to protect it from damage due...

Page 14: ...at the output 2 At rated voltage cos 0 8 at the output values for different speci cations on request 3 Max supply side line fuse according to DIN EN 60204 1 classi cation VDE0113 chapter 1 Line voltag...

Page 15: ...pendent on ambient temperature and line voltage The maximum permissible temperature for the rated current at rated voltage is speci ed as rated temperature Since the dissipation of the power loss heat...

Page 16: ...ernal thermostats 2 TB 1 Kontaktbelastung Contact rating max AC 250 V 2 A 5 3 UMPO09K13 17 03 2015 FRQ5S E 6 10A 22 24 21 BU RD BK 0 1 2 3 5 4 1 Line 1 208 277 V 50 60 Hz 2 1 Motor with internal therm...

Page 17: ...ve any questions concerning the use of our products or plan special uses please contact Systemair Industriev gen 3 73930 Skinnskatteberg Telefon 46 0 222 440 00 Telefax 46 0 222 440 99 mailbox systema...

Reviews: