22
i.1.7
Roof
unit
with
steel
roof
For
units
with
steel
plate
roof,
the
steel
plates
are
delivered
uninstalled
on
a
separate
pallet.
Do
not
step
or
walk
on
the
plates.
i.1.8
Pre
‐
assembly
storage
The
AHU
must
be
protected
from
the
weather
and
accidental
impact.
Plastic
packaging
must
be
removed
and
the
unit
covered
with
tarpaulin
or
similar
materials.
In
order
to
minimize
condensation,
sufficient
air
circulation
must
be
ensured
between
the
covering
and
the
unit.
i.1.9
Tilt
less
than
30
˚
during
transportation
of
the
section
with
heat
pump
–
DVU
During
transportation,
the
unit
section
‐
DVU
must
always
be
in
the
upright
position
or
tilted
less
than
30
˚
.
If
it
is
necessary
to
tilt
the
unit
more
than
30
˚
,
the
suction
pipe
of
the
compressor
must
point
upwards
to
prevent
the
escape
of
oil
from
the
compressor
sump.
i.2.
Installation
‐
mechanical
i.2.1
Free
area
in
front
of
and
above
the
unit
Important!
When
positioning
the
unit
on
the
site,
it
must
be
ensured
that
an
area
with
the
same
width
as
the
unit
is
kept
free
for
service
and
inspection
and
also
for
replacement
of
fans
and
exchanger,
if
needed.
The
width
of
the
free
area
must
be
at
least
900
mm.
Important!
For
safe
access
to
the
cabinet
with
electrical
components,
if
the
cabinet
is
placed
on
top
of
the
unit,
the
free
area
from
the
upper
edge
of
the
cabinet
to
the
ceiling
must
be
at
least
700
mm.
i.2.2
Supporting
surface
The
surface
beneath
the
unit
must
be
level,
horizontal
and
vibration
‐
free.
The
surface
must
be
able
to
withstand
the
load
of
the
AHU.
Weights
of
the
sections
are
written
in
Annex
2.
Remember!
Duct
work
must
be
sound
insulated
and
must
not
be
mounted
directly
on
beams,
trusses
or
other
critical
building
parts.
i.2.3
Adjustable
feet
under
legs
or
base
frame
and
transport
of
sections
Adjustable
feet
are
provided
in
a
carton
box
placed
inside
the
unit.
Adjustable
feet
are
delivered
for
indoor
units
and
not
for
outdoor
units.
Sections
can
be
transported
on
the
site
by
hand
manual
forklifts
or
similar.
The
frame
profiles
in
the
edges
of
the
sections
have
carrying
capacity
for
lifting
by
the
hand
manual
forklifts.
Summary of Contents for Danvent DV-10
Page 16: ...15 DVE Plug fan DVD Silencer DVX Humidifier...
Page 57: ...56...
Page 84: ...8 8...
Page 88: ...9 4 9 1 3 Information about connection of cables to terminals on the control board...
Page 91: ...9 7...
Page 103: ...9 19...
Page 111: ...12 3...
Page 115: ...12 7 Frequency converter is always necessary for the control of each PM motor...
Page 119: ...13 1 Annex 13 Commissioning See separate cover with annexes 1 2 3 and 13...