12—5
12.4
Set
‐
up
Danfoss
FC101
for
DV
‐
units
with
PM
motors
SETUP
IS
DONE
IN
FACTORY
BEFORE
DELIVERY
To
reload
Systemair
factory
settings
from
the
control
panel:
0
‐
50:
LCP
Copy:
[2]
Systemair
factory
set
‐
up
is
based
on
Danfoss
initialization.
14
‐
22:
Operation
mode:
[2]
Initialisation
(Danfoss
Initialisation)
Turn
power
off
and
on.
Systemair
factory
set
‐
up:
0
‐
01:
Language
selection:
1
‐
06:
Clockwise
Direction:
[1]
Inverse
1
‐
10:
Motor
Construction:
[1]
PM,
non
‐
salient
SPM
1
‐
24:
Motor
Current:
According
to
motor
plate
/
Schedule
1
‐
25:
Motor
Nominal
Speed:
According
to
motor
plate
/
Schedule
1
‐
26:
Motor
Cont.
Rated
torque:
According
to
motor
plate
/
Schedule
1
‐
30:
Stator
Resistance
(Rs):
According
to
motor
plate
/
Schedule
1
‐
37:
d
‐
axis
inductance
(Ld):
According
to
motor
plate
/
Schedule
1
‐
39:
Motor
Poles:
According
to
motor
plate
/
Schedule
1
‐
40:
Back
EMF
at
1000
RPM:
According
to
motor
plate
/
Schedule
1
‐
42:
Motor
Cable
Length:
3m
1
‐
73:
Flying
start:
[1]
Enabled
1
‐
90:
Motor
Thermal
Protection:
[2]
Thermistor
trip
3
‐
15:
Reference
1
Source:
[2]
Analog
input
AI54
1
‐
93:
Thermistor
Source:
[1]
Analog
input
AI53
3
‐
03:
Maximum
Reference:
According
to
motor
plate
/
Schedule
3
‐
16
+
3
‐
17:
Reference
2
‐
and
3
Source:
[0]
No
function
3
‐
41:
Ramp
1
Up:
According
to
schedule
for
PM
motor
parameters
‐
below
3
‐
42:
Ramp
1
down:
According
to
schedule
for
PM
motor
parameters
‐
below
4
‐
19:
Max.
Output
Frequency:
According
to
motor
plate
/
Schedule
4
‐
14:
Motor
Speed
High
Limit:
According
to
motor
plate
/
Schedule
5
‐
12:
Terminal
27
Digital
input:
[0]
No
operation
5
‐
40.0:
Function
Relay:
[3]
Drive
ready/remote
5
‐
40.1:
Function
Relay:
[3]
Drive
ready/remote
6
‐
25:
Terminal
54
High
Reference:
According
to
motor
plate
/
Schedule
14
‐
20:
Reset
Mode:
[2]
Automatic
reset
x
2
2
‐
01:
DC
brake
current:
100
%
2
‐
02:
DC
braking
time:
20.0
sec.
2
‐
07:
Parking
time:
10,0
sec.
0
‐
50:
LCP
Copy:
[1]
All
to
LCP
(Copy
of
Systemair
factory
settings
to
panel)
Connections:
0
‐
10V:
Terminal
54
‐
55
and
Start:
Terminal
12
‐
18
as
well
as
Thermistor:
Terminal
50
‐
53
Drive
ready:
Terminal
1
‐
2
Summary of Contents for Danvent DV-10
Page 16: ...15 DVE Plug fan DVD Silencer DVX Humidifier...
Page 57: ...56...
Page 84: ...8 8...
Page 88: ...9 4 9 1 3 Information about connection of cables to terminals on the control board...
Page 91: ...9 7...
Page 103: ...9 19...
Page 111: ...12 3...
Page 115: ...12 7 Frequency converter is always necessary for the control of each PM motor...
Page 119: ...13 1 Annex 13 Commissioning See separate cover with annexes 1 2 3 and 13...