9—2
The
factory
sets
the
positions
of
the
8
DIP
switch
levers
for
the
maximum
of
20
revolutions
per
minute
for
sorption
exchangers.
The
position
of
each
DIP
switch
lever
is
shown
below.
Rotor
20
rpm
Sorption
(HM)
rotors
from
Hoval
DV
Position
of
DIP
switches
Diameter
of
pulley
for
rotors
from
Hoval
Motor
type
1
2
3
4
5
6
7
8
10
1
0
0
0
0
0
0
0
65
90TYD
‐
S214
‐
M
15
1
0
0
0
0
0
0
0
65
20
1
0
0
0
0
0
0
0
98
25
1
0
0
0
0
0
0
0
98
30
0
1
0
0
0
0
0
0
112
120TYD
‐
S214
‐
M
40
0
1
0
0
0
0
0
0
118
50
1
1
0
0
0
0
0
0
118
60
1
1
0
0
0
0
0
0
132
80
0
0
1
0
0
0
0
0
150
120TYD
‐
S214
‐
L
100
1
0
1
0
0
0
0
0
150
120
1
0
1
0
0
0
0
0
160
150
0
1
1
0
0
0
0
0
150
190
0
1
1
0
0
0
0
0
180
240
0
1
1
0
0
0
0
0
180
9.1.2
Indication
of
operation
mode
via
red
and
green
LED
as
well
as
test
of
motor
The
LED
is
in
the
cover
of
the
cabinet.
LED
indication
Value
No
indication
Power
off
Green
Ordinary
operation
Green
–
flashes
Ready
for
operation
Constant
green
and
a
short
red
flash
Rotor
guard
is
activated
for
the
short
red
flash
by
one
bolt
on
the
rotor.
By
counting
the
number
of
red
flashes
during
one
minute,
you
hereby
check
the
number
of
revolutions
per
minute.
Red
flashes
in
series
See
explanation
below
Red
Alarm
due
to
internal
error.
Is
still
operating
for
some
minutes
Number
of
red
flashes
in
series
Value
1
Over
current
2
Over
voltage
3
Under
voltage
4
Failure
in
the
controller
Summary of Contents for Danvent DV-10
Page 16: ...15 DVE Plug fan DVD Silencer DVX Humidifier...
Page 57: ...56...
Page 84: ...8 8...
Page 88: ...9 4 9 1 3 Information about connection of cables to terminals on the control board...
Page 91: ...9 7...
Page 103: ...9 19...
Page 111: ...12 3...
Page 115: ...12 7 Frequency converter is always necessary for the control of each PM motor...
Page 119: ...13 1 Annex 13 Commissioning See separate cover with annexes 1 2 3 and 13...