12—4
12.3
AC
‐
fan
operation
without
thermistor
for
Danfoss
FC101
Systemair
factory
set
‐
up
is
based
on
Danfoss
initialization.
14
‐
22:
Operation
mode:
[2]
Initialisation
(Danfoss
Initialisation)
Turn
power
off
and
on.
Systemair
factory
set
‐
up:
0
‐
01:
Language
selection:
1
‐
03:
Torque
characteristic:
[3]
Auto
‐
Energy
optim.
1
‐
20:
Motor
power:
According
to
motor
plate
1
‐
24:
Motor
Current:
According
to
motor
plate
1
‐
25:
Motor
Nominal
Speed:
According
to
motor
plate
1
‐
29:
Automatic
motor
adption
(AMA):
[1]
Kompl.motor
adaption
to
(Turn
power
off
and
on.)
1
‐
42:
Motor
Cable
Length:
Order
specific
1
‐
50:
Motor
Magnetisation
at
zero
speed.:
0
%
1
‐
52:
Min.
Speed
Normal
Magnetisation:
10
Hz
1
‐
73:
Flying
start:
[1]
Enable
5
‐
40.0:
Function
Relay:
[3]
Drive
ready/remote
14
‐
03:
Over
modulation:
[1]
Active
14
‐
20:
Reset
Mode:
[2]
Automatic
reset
x
2
0
‐
50:
LCP
Copy:
[1]
All
to
LCP
(Copy
of
Systemair
factory
settings
to
panel)
Connections:
0
‐
10V:
terminal
54
‐
55
Start:
terminal
12
‐
18
Drive
ready:
terminal
1
‐
2
Jumper
terminal
12
‐
27
Summary of Contents for Danvent DV-10
Page 16: ...15 DVE Plug fan DVD Silencer DVX Humidifier...
Page 57: ...56...
Page 84: ...8 8...
Page 88: ...9 4 9 1 3 Information about connection of cables to terminals on the control board...
Page 91: ...9 7...
Page 103: ...9 19...
Page 111: ...12 3...
Page 115: ...12 7 Frequency converter is always necessary for the control of each PM motor...
Page 119: ...13 1 Annex 13 Commissioning See separate cover with annexes 1 2 3 and 13...