9—13
9.3.5
Measurement.
The
hub
with
radial
walls
must
be
aligned
both
vertically
and
horizontally
with
the
casing.
If
measurement
indicates
that
there
are
discrepancies,
the
radial
walls,
and
possibly
also
the
hub,
will
need
to
be
adjusted.
Start
measuring
at
the
upper
radial
wall.
Measure
the
distances
A
and
B
between
the
radial
walls
and
the
casing
at
points
1
,
2
,
3
and
4
.
Measure
similar
points
on
the
next
radial
wall.
Check
that
values
A
and
B
are
the
same
for
both
radial
walls
at
all
points
and
that
these
values
match
approved
tolerances.
2
If
the
tolerance
is
not
achieved,
undo
the
screw
at
the
wing
of
the
hub
and
adjust
the
radial
wall
horizontally.
4
A
B
3
Approved
tolerances:
A=B±1