12—10
*K1:
programmed
function
at
factory:
Fault
indication
not
inverted
LED Code
Relays K1*
Cause
OFF
de-energized, 11 - 14 interrupted
No line voltage
ON
energized, 11 - 14 bridged
Normal operation without fault
1 x
energized, 11 - 14 bridged
No enable = OFF
2 x
energized, 11 - 14 bridged
Temperature management active
3 x
de-energized, 11 - 14 interrupted
HALL-IC error
4 x
de-energized, 11 - 14 interrupted
Line failure
(only for 3 ~ types)
5 x
de-energized, 11 - 14 interrupted
Motor blocked
6 x
de-energized, 11 - 14 interrupted
IGBT Fault
7 x
de-energized, 11 - 14 interrupted
Intermediate circuit undervoltage
8 x
de-energized, 11 - 14 interrupted
Intermediate circuit overvoltage
9 x
energized, 11 - 14 bridged
IGBT cooling down period
11 x
de-energized, 11 - 14 interrupted
Error motor start
12 x
de-energized, 11 - 14 interrupted
Line voltage too low
13 x
de-energized, 11 - 14 interrupted
Line voltage too high
14 x
de-energized, 11 - 14 interrupted
Error Peak current
17 x
de-energized, 11 - 14 interrupted
Temperature alarm
Summary of Contents for Danvent DV-10
Page 16: ...15 DVE Plug fan DVD Silencer DVX Humidifier...
Page 57: ...56...
Page 84: ...8 8...
Page 88: ...9 4 9 1 3 Information about connection of cables to terminals on the control board...
Page 91: ...9 7...
Page 103: ...9 19...
Page 111: ...12 3...
Page 115: ...12 7 Frequency converter is always necessary for the control of each PM motor...
Page 119: ...13 1 Annex 13 Commissioning See separate cover with annexes 1 2 3 and 13...