12—2
12.2
Set
‐
up
for
Danfoss
FC101
for
DV
‐
units
with
AC
motors
SETUP
IS
DONE
IN
FACTORY
BEFORE
DELIVERY
To
reload
Systemair
factory
settings
from
the
control
panel:
0
‐
50:
LCP
Copy:
[2]
Systemair
factory
set
‐
up
is
based
on
Danfoss
initialization.
14
‐
22:
Operation
mode:
[2]
Initialisation
(Danfoss
Initialisation)
Turn
power
off
and
on.
Systemair
factory
set
‐
up:
0
‐
01:
Language
selection:
1
‐
03:
Torque
characteristic:
Single
fan:
[3]
Auto
‐
Energy
optim.
With
twin
fan
set
‐
up:
[1]
Variable
Torque
1
‐
20:
Motor
Power:
According
to
motor
plate
/
order
papers
With
twin
fan
set
‐
up
total
power
must
be
used
1
‐
24:
Motor
Current:
According
to
motor
plate
/
order
papers
With
twin
fan
set
‐
up
total
current
must
be
used
1
‐
25:
Motor
Nominal
Speed:
According
to
motor
plate
/
order
papers
1
‐
42:
Motor
Cable
Length:
3m
1
‐
50:
Motor
Magnetisation
at
zero
speed.:
0
%
1
‐
52:
Min.
Speed
Normal
Magnetisation:
10
Hz
1
‐
73:
Flying
Start:
[1]
Enable
1
‐
90:
Motor
Thermal
Protection:
[2]
Thermistor
trip
3
‐
15:
Reference
1
Source:
[2]
Analog
input
AI54
1
‐
93:
Thermistor
Source:
[1]
Analog
input
AI53
3
‐
03:
Maximum
Reference:
Max.
Hz
from
order
papers
3
‐
16
+
3
‐
17:
Reference
2
‐
and
3
Source:
[0]
No
function
3
‐
41:
Ramp
1
up:
60
Sec.
3
‐
42:
Ramp
1
down:
30
Sec.
4
‐
19:
Max.
Output
Frequency:
90Hz
4
‐
14:
Motor
Speed
High
Limit:
90Hz
5
‐
12:
Terminal
27
Digital
input:
[0]
No
operation
5
‐
40.0:
Function
Relay:
[3]
Drive
ready/remote
5
‐
40.1:
Function
Relay:
[3]
Drive
ready/remote
6
‐
25:
Terminal
54
High
Reference:
Max.
Hz
from
order
papers
14
‐
20:
Reset
Mode:
[2]
Automatic
reset
x
2
0
‐
50:
LCP
Copy:
[1]
All
to
LCP
(Copy
of
Systemair
factory
settings
to
panel)
Connections:
0
‐
10V:
terminal
54
‐
55
Start:
terminal
12
‐
18
Thermistor:
terminal
50
‐
53
Drive
ready:
terminal
1
‐
2
Summary of Contents for Danvent DV-10
Page 16: ...15 DVE Plug fan DVD Silencer DVX Humidifier...
Page 57: ...56...
Page 84: ...8 8...
Page 88: ...9 4 9 1 3 Information about connection of cables to terminals on the control board...
Page 91: ...9 7...
Page 103: ...9 19...
Page 111: ...12 3...
Page 115: ...12 7 Frequency converter is always necessary for the control of each PM motor...
Page 119: ...13 1 Annex 13 Commissioning See separate cover with annexes 1 2 3 and 13...