BPS H-ES

Horizontal Boxer Packaged Solution  
with EcoSmart Classic (ES) Control 

Installation Manual

1.0 SAFETY INFORMATION

• 

The provision of the electrical supply and the connection of the unit to the mains must be 
carried out by a qualified electrician.

• 

Isolate from power supply before removing any covers. During installation / maintenance ensure 
all covers are fitted before switching on the mains supply. 

• 

All-pole disconnection from the mains as shown in the wiring diagram must be incorporated 
within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with 
latest edition of the wiring regulations.

• 

This unit must be earthed.

• 

Ducting must be securely fixed with screws to the spigot to prevent access to live parts. Duct 
runs terminating close to the fan must be adequately protected by suitable guards.

• 

If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or 
similarly qualified persons in order to avoid a hazard.

• 

Precautions must be taken to avoid the back-flow of gases into the room from the open flue of 
gas or other fuel-burning appliances.

• 

This appliance should not be used by children or persons with reduced physical, sensory or 
mental capabilities or lack of experience and knowledge, unless they have been given supervision 
or instruction concerning the safe use of the appliance by a person responsible for their safety. 
Children shall not play with the appliance. Cleaning and user maintenance shall not be carried 
out by children.

1.1 Symbols

 

GENERAL WARNING 

 

 

Signifies a general warning regarding hazard specified by supplementary information.

 

ELECTRIC SHOCK

 

 

 

This unit must be completely electrically isolated before any panels are removed. Check  

 

 

mains supply and control connections. 

 

ROTATING PARTS 

 

 

 

This unit contains fast moving rotational parts which may start automatically. It is the  

 

 

sole responsibility of the installer to adequately guard these components.

 

REFER TO INSTRUCTION MANUAL

 

 

 

Read and understand the installation and maintenance manual before installing,    

 

 

operating or maintaining this product.

Summary of Contents for BPS H-ES Series

Page 1: ...manufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel...

Page 2: ...uld always recommend a site specific risk assessment by a competent person to determine if any additional PPE is required 2 0 INTRODUCTION The information contained in this document provides details o...

Page 3: ...ust Right Handed for Horizontal PHX Units Frost Coil Electric 2 B AH FE R BPS size Frost Coil Electric 36kW Right Handed for Horizontal PHX Units B AH FE L BPS size Frost Coil Electric 36kW Left Hande...

Page 4: ...tions will have 50mm square lifting holes at the end of each side to enable lifting In addition to this covered fork lifting channels are located across the width of the base frame if the module lengt...

Page 5: ...additional time should be allocated For convenience it is preferred that wherever possible this minimum access provision is not adopted and it is recommended that a minimum of around 600mm clearance a...

Page 6: ...ct Supply Model shown is left handed EXTRACT SUPPLY INTAKE DISCHARGE Access Shown from top Left hand L Access CONTROLS LPHW 600mm 600mm 8 Top View of Access For Left Hand Units 5 2 2 Right Hand Units...

Page 7: ...e required leakage classification Door locking mechanisms may also have to be adjusted Nuaire cannot be held responsible for the units failing a site leakage test if the above have not been carried ou...

Page 8: ...ork connections with units instead the open ended framework should be utilised Flanged connections are available as an option refer to technical documents for information relating specifically to the...

Page 9: ...the requirement of removing the roof terminal Figure 18 17 Removing Roof Terminal 18 Actuator Access 6 10 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled f...

Page 10: ...connected If inlet and outlet dampers are fitted remove the damper link wires This will allow a 1 minute delay before starting the fans 7 4 1 Switch Live Switch Live SL terminal A signal of 100 230V...

Page 11: ...electric heating Section 7 8 5 7 6 1 Code Description B 8 05 H L R ES L 1 2 3 4 5 6 7 8 1 Range B Boxer Packaged Solution 2 ErP Compliance Year 8 or No Affix 2018 9 Unit Size 05 10 15 or 20 10 Heat Re...

Page 12: ...Number 671827 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H ES Installation Manual 7 8 Wiring Diagrams 7 8 1 Unit Sizes 05 20 with No Heating 25 Unit Sizes 05 20 with No Hea...

Page 13: ...g Fault Frost Tx Rx Extract Fan Board Condensate Pump HX Bypass Relay Lighting Thermal Wheel Transformer 230Vac Supply Fan Contactor Extract Fan Contactor 0 24V 15V 0 15V 230V 400V ecosmart Min Trickl...

Page 14: ...n 2 H e a ti n g C o o li n g F a u lt F ro s t T x R x 0 24V 15V 0 15V 230V 400V Condensate Pump HX Bypass Relay Heat Exchanger Bypass Board ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0F...

Page 15: ...ment Number 671827 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H ES Installation Manual 7 8 4 Unit Sizes 05 10 with Electric Heating 28 Unit Sizes 05 10 with Electric Heating...

Page 16: ...ment Number 671827 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H ES Installation Manual 7 8 5 Unit Sizes 15 20 with Electric Heating 29 Unit Sizes 15 20 with Electric Heating...

Page 17: ...otection It connects to the main unit via plug and play interconnecting looms see Section 6 4 No external connections are required Electric heater elements are protected by a fail safe over temperatur...

Page 18: ...ing Cooling Fault Frost TX RX Connector Ecosmart 32 Ecosmart Commissioning Board 9 4 Settings 9 4 1 Maximum Airflow Ensure the power supply is switched off and that a link wire is connected from the s...

Page 19: ...duty operation maintenance intervals are to be established by the operator 11 4 Filters When removing the filter access panels pay attention to the airflow direction marked on the panel this must be...

Page 20: ...ersonnel for details 11 7 Legionella Check Legionella risk management should be undertaken by a competent person appointed by the duty holder in accordance with the latest edition of the HSE approved...

Page 21: ...ner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compon...

Page 22: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...