26. 08. 21. Document Number  671827

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BPS H-ES

Installation Manual

6.0 MECHANICAL INSTALLATION

Installation must be completed by competent persons, in accordance 
with good industry practice and should conform to all governing and 
statutory bodies i.e. IEE, CIBSE, etc.

The unit should stand upright and level on the floor, foundation 
or supporting steelwork which should be rigid, flat and level and 
should be capable of supporting the weight of the unit including 
water or refrigerant in the coils. Nuaire takes no responsibility for the 
coordination of support.

6.1 Unit Location

To prevent possible reintroduction of contaminated air through the 
outside air intake, the unit should be located away from building flue 
stacks or exhaust ventilators.

Once assembled and in position, sufficient free space must be available 
adjacent to the unit for future inspection, maintenance, component 
service, repair and replacement and connection of services. It is 
recommended that at least the unit width (vertically arranged units) 
+ 100mm be allowed. A minimum of 600mm is required for regular 
maintenance.

Sufficient clearance for U-traps on condensate drain and overflow  
connections should also be considered by the purchaser.

6.2 Air Leakage

Loading, transportation, off loading and site positioning can cause 
the air handling unit structures to move, therefore panel seals will not 
always remain fully intact.

It is inevitable that in such cases, re-sealing of the units panels and 
joints may have to be carried out on site for the air-handling units to 
achieve the required leakage classification. Door locking mechanisms 
may also have to be adjusted.

Nuaire cannot be held responsible for the units failing a site leakage 
test if the above have not been carried out correctly.

6.3 Module Joints

After unwrapping, temporarily remove the rubber weatherproof cover 
strip and M10 base frame bolts from any modules and store in a safe 
location for later use.

Apply the sealing gasket as necessary to the mating faces of the 
unit frames. Typically the sealing gaskets are pre-fitted to the heat 
exchanger module; ancillary modules will be provided with a roll of 
sealing gasket for on-site fitting.

Make the unit joints in the following order:

Left and right hand side M10 bolts between the modules’ base 
frames (Figure 11).

Left and right hand side M6 Lower 3 axis alignment clamps (Figure 
12).

Left and right hand side M6 Middle 3 axis alignment clamps.

Left and right hand side M6 Upper 3 axis alignment clamps.

Air leakage, air blow marks to the unit casings and unacceptable 
noise levels could result if the correct installation procedures are not 
employed.

11 

M10 Modular Base Frame Connection Bolt

12 

3-Axis Clamp

6.4 Internal Connections

There are a number of internal connections that need to be completed 
prior to starting/commissioning the unit. These consist of all the wiring 
connections and the condensate hose (plate heat exchanger option 
only).

Ensure that the condensate hose is connected between modules. Care 
must be taken to ensure a constant fall in gradient is maintained and 
the hose is kept taught (Figure 13).

Access is available in the fan plate to allow electrical/wiring 
connections to be made between modules (Figure 14).

When making the wiring connections, the sensor loop (Figure 15) must 
be removed and relocated to the end of the unit. 

13 

Condensate Hose Connection

Summary of Contents for BPS H-ES Series

Page 1: ...manufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel...

Page 2: ...uld always recommend a site specific risk assessment by a competent person to determine if any additional PPE is required 2 0 INTRODUCTION The information contained in this document provides details o...

Page 3: ...ust Right Handed for Horizontal PHX Units Frost Coil Electric 2 B AH FE R BPS size Frost Coil Electric 36kW Right Handed for Horizontal PHX Units B AH FE L BPS size Frost Coil Electric 36kW Left Hande...

Page 4: ...tions will have 50mm square lifting holes at the end of each side to enable lifting In addition to this covered fork lifting channels are located across the width of the base frame if the module lengt...

Page 5: ...additional time should be allocated For convenience it is preferred that wherever possible this minimum access provision is not adopted and it is recommended that a minimum of around 600mm clearance a...

Page 6: ...ct Supply Model shown is left handed EXTRACT SUPPLY INTAKE DISCHARGE Access Shown from top Left hand L Access CONTROLS LPHW 600mm 600mm 8 Top View of Access For Left Hand Units 5 2 2 Right Hand Units...

Page 7: ...e required leakage classification Door locking mechanisms may also have to be adjusted Nuaire cannot be held responsible for the units failing a site leakage test if the above have not been carried ou...

Page 8: ...ork connections with units instead the open ended framework should be utilised Flanged connections are available as an option refer to technical documents for information relating specifically to the...

Page 9: ...the requirement of removing the roof terminal Figure 18 17 Removing Roof Terminal 18 Actuator Access 6 10 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled f...

Page 10: ...connected If inlet and outlet dampers are fitted remove the damper link wires This will allow a 1 minute delay before starting the fans 7 4 1 Switch Live Switch Live SL terminal A signal of 100 230V...

Page 11: ...electric heating Section 7 8 5 7 6 1 Code Description B 8 05 H L R ES L 1 2 3 4 5 6 7 8 1 Range B Boxer Packaged Solution 2 ErP Compliance Year 8 or No Affix 2018 9 Unit Size 05 10 15 or 20 10 Heat Re...

Page 12: ...Number 671827 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H ES Installation Manual 7 8 Wiring Diagrams 7 8 1 Unit Sizes 05 20 with No Heating 25 Unit Sizes 05 20 with No Hea...

Page 13: ...g Fault Frost Tx Rx Extract Fan Board Condensate Pump HX Bypass Relay Lighting Thermal Wheel Transformer 230Vac Supply Fan Contactor Extract Fan Contactor 0 24V 15V 0 15V 230V 400V ecosmart Min Trickl...

Page 14: ...n 2 H e a ti n g C o o li n g F a u lt F ro s t T x R x 0 24V 15V 0 15V 230V 400V Condensate Pump HX Bypass Relay Heat Exchanger Bypass Board ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0F...

Page 15: ...ment Number 671827 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H ES Installation Manual 7 8 4 Unit Sizes 05 10 with Electric Heating 28 Unit Sizes 05 10 with Electric Heating...

Page 16: ...ment Number 671827 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk BPS H ES Installation Manual 7 8 5 Unit Sizes 15 20 with Electric Heating 29 Unit Sizes 15 20 with Electric Heating...

Page 17: ...otection It connects to the main unit via plug and play interconnecting looms see Section 6 4 No external connections are required Electric heater elements are protected by a fail safe over temperatur...

Page 18: ...ing Cooling Fault Frost TX RX Connector Ecosmart 32 Ecosmart Commissioning Board 9 4 Settings 9 4 1 Maximum Airflow Ensure the power supply is switched off and that a link wire is connected from the s...

Page 19: ...duty operation maintenance intervals are to be established by the operator 11 4 Filters When removing the filter access panels pay attention to the airflow direction marked on the panel this must be...

Page 20: ...ersonnel for details 11 7 Legionella Check Legionella risk management should be undertaken by a competent person appointed by the duty holder in accordance with the latest edition of the HSE approved...

Page 21: ...ner pieces plastic heat exchangers packaging material and other plastic components can be segregated into mixed plastic and widely recycled Cardboard packaging wood used filters and other paper compon...

Page 22: ...te provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Am...

Reviews: