Chapter 6 Maintaining and Troubleshooting the TimeProvider
Troubleshooting the TimeProvider
174
TimeProvider User’s Guide
097-58001-02 Revision G – April 2008
Table 6-6
describes the alarm codes and their set and clear conditions.
Table 6-6. Set and Clear Conditions for Alarms
Alarm ID
Set Alarm Conditional Description
Clear Alarm Conditional Description
SYS Codes
COMPAT
System components are incompatible
System components are compatible
EXPFAIL
Expansion connectivity failed
Expansion connectivity restored
PWRA
Power A Failed
Power A Restored
PWRB
Power B Failed
Power B Restored
EXTALM1
External Alarm 1 set
External Alarm 1 cleared
EXTALM2
External Alarm 2 set
External Alarm 2 cleared
IOC1EQPT
IOC1 removed from the shelf
IOC1 reinstalled
IOC2EQPT
IOC2 removed from the shelf
IOC2 reinstalled
IMC Codes
IOC1COMM
IMC to IOC1 communication failed
IMC to IOC1 communication established
IOC2COMM
IMC to IOC2 communication failed
IMC to IOC2 communication established
IMCFAIL
Summary alarm of BIST faults
IOC1 Codes
IOC1COMM
IOC1 to IMC communication failed
IOC1 to IMC communication established
IOC1TO2COMM
IOC1 to IOC2 communication failed
IOC1 to IOC2 communication established
IOCFAIL
IOC hardware failure
IOC hardware restored
BTBCKUP
BesTime backup reference disqualified
BesTime backup sources qualified
CLKBRDG
Clock is in Bridging mode
Clock exited Bridging mode
CLKFREE
Clock entered Free-run mode
Clock exited Free-run mode
CLKHOLD
Clock entered Holdover mode
Clock exited Holdover mode
CLKWARM
Clock entered Warm-up mode
Clock exited Warm-up mode
SYNTHEOR
Output generator exceeded pull-in
range
Output generator within pull-in range
IOC2 Codes
IOC2COMM
IOC2 to IMC communication failed
IOC2 to IMC communication established
IOC2TO1COMM
IOC2 to IOC1 communication failed
IOC2 to IOC1 communication established
IOCFAIL
IOC hardware failure
IOC hardware restored