Chapter 4 Provisioning the TimeProvider
Provisioning Alarms
128
TimeProvider User’s Guide
097-58001-02 Revision G – April 2008
CLKWARM
Local oscillator on the
specified IOC is in
Warm-up mode
MN | MJ
IMMED
No
MN
MN
CLKFREE
Local oscillator on
specified IOC is in
Free-run mode
MN | MJ |
CR
IMMED
No
MJ
MJ
CLKBRDG
Local oscillator on
specified IOC is in
Bridging mode
MN | MJ |
CR
IMMED
No
MJ
MJ
CLKHOLD
Local oscillator on
specified IOC is in
Holdover mode
MN | MJ |
CR
IMMED
No
MJ
MJ
<aid> = PRS
INPDISQ
Specified input has
been disqualified or
qualified as a possible
system reference.
MN | MJ |
CR
FLT
DELAY
Yes
MN
MN
INPLOS
Specified input has
Loss Of Signal.
1
MN | MJ |
CR
IMMED
No
MN
MN
INPFRQ
Specified input has
calculated received
frequency that exceeds
the pull-in range of the
LO.This alarm condition
disqualifies the input as
a possible reference.
2
NR | NA |
MN | MJ |
CR
IMMED
No
MN
NR
INPPHASE
Specified input port’s
phase measurement
exceeds usable value.
NR | NA |
MN | MJ |
CR
IMMED
No
MN
MN
EXDSC
Input has had excessive
discontinuities, indicated
by more than 3 signal
faults (OOF, BPV, CRC,
or AIS) within a 5-minute
window. The alarm
clears when the
5-minute window
contains less than 3
signal faults.
NR | NA |
MN | MJ |
CR
IMMED
No
MN
MN
Table 4-3. Alarm Conditions and Defaults (Continued)
Alarm ID
Description of Alarm
Condition
Possible
Alarm
Levels
Error
Delay
Default
Error
Delay
Editable?
Default Level
SSU
Mode
SUB
Mode