A-96.250.231 / 130421
AMI Turbitrack
Program List and Explanations
53
3.2 Rinsing
3.2.1
Manual operation
Start rinsing manually at any time.
3.2.2
Automatic
3.2.2.1
Mode
: The following modes are available:
Interval
daily
weekly
off
3.2.2.201
Run time
: The run time can be set in steps of 10 seconds from
30–1800 seconds.
3.2.2.30
Interval
: Set the interval length with the [
] or [
] key. Pos
-
sible intervals are:1, 2, 3, 4, 6, 8 or 12 h.
3.2.2.211
Run time
: The run time can be set in steps of 10 seconds from
30–1800 seconds.
3.2.2.31
Start time
: The start time can be set daily at any time of a day with
the [
] or [
] key.
Range: 00:00:00–23:59:59
3.2.2.221
Run time
: The run time can be set in steps of 10 seconds from
30–1800 seconds.
3.2.2.32
Calendar
:
3.2.2.32.1
Start time
: The programmed start time is valid for each of the pro
-
grammed days. To set the start time, see
.
3.2.2.32.2
Monday
: Possible settings, on or off
to
3.2.2.32.8
Sunday
: Possible settings, on or off
The automatic rinsing is switched off.
3.2.2.1
Mode Interval
5.3.2.1
Mode daily
5.3.2.1
Mode weekly
5.3.2.1
Mode off