75
Malfunction
Description
Remedies
101:U-DC max
Your AT solar inverter is ap-
proved for a maximum open-
circuit voltage of the solar
generator of 680 V. All com-
ponents of the DC input are
sufficiently dimensioned with
a safety factor. If the threshold
is exceeded, the solar inverter
stops feeding.
The maximum DC voltage
was exceeded.
➡
Check the dimensioning of
your PV generator.
Too many modules are con-
nected in series.
➡
Reduce the number of mo-
dules and carry out commis-
sioning again.
102:Insulation
Before each connection, your
solar inverter checks the PV sys-
tem for a possible earth fault
or insulation faults. Should this
kind of error be detected, no
feeding takes place. The mode
of operation is conformant
with DIN VDE 0126-1-1.
The solar inverter has disco-
vered an insulation fault in the
PV system during start-up.
➡
Check your PV system for
possible insulation faults
(pinched-off DC lines etc).
The measured insulation
resistance must be at least
680 kohms.
75
Malfunction
Description
Remedies
103:AFI>30mA
Your solar inverter is equipped
with a universally sensitive AFI
according to DIN VDE 0126-
1-1. This monitoring unit has
detected a relative residual
current jump of >30 mA.
A residual current jump has oc-
curred during operation of the
solar inverter.
➡
Check your PV system for
possible insulation faults.
104:AFI>0.3A
Your solar inverter is equipped
with a universally sensitive AFI
according to DIN VDE 0126-
1-1. This monitoring unit has
detected an absolute residual
current of >300 mA.
A residual current greater than
300 mA has occurred during
operation of the solar inverter.
➡
Check your PV system for
possible insulation faults.
201:Surgef.
Your solar inverter continually
monitors the quality of the AC
grid. During high voltage peaks
on the phase feeding in, the
solar inverter stops feeding and
attempts a restart.
The solar inverter has detected
a high voltage peak on the
phase feeding in.
➡
After malfunction elimina-
tion the solar inverter re-
starts automatically. Should
the error occur frequently,
please contact your power
supply company.
A monitoring phase and a di-
rectly earthed conductor were
exchanged when connecting
the AC side.
Summary of Contents for AT 2700
Page 1: ...User Manual for Sunways Solar Inverter AT 5000 AT 4500 AT 3600 AT 2700...
Page 8: ...1 0 Product Description...
Page 16: ...16 2 0 Safety precautions...
Page 22: ...22 3 0 Installation...
Page 46: ...46 4 0 Commissioning...
Page 56: ...56 5 0 Operation...
Page 96: ...96 6 0 System monitoring...
Page 129: ...129...
Page 130: ...130 7 0 Appendix...
Page 135: ...135 Efficiency of AT 5000 Output power W...
Page 136: ...136 Efficiency of AT 4500 Output power W...
Page 137: ...137 Efficiency of AT 3600 Output power W...
Page 138: ...138 Efficiency of AT 2700 Output power W...
Page 140: ......
Page 141: ...C F Werbung und Dokumentation Villingen Schwenningen www cundf de...