23
3.1 Mechanical installation
Requirements for installation location
!
DANGER
The solar inverter may not be installed in
rooms subject to explosion hazards.
The solar inverter may not be exposed to
caustic gases!
No combustible or highly flammable
materials may be stored within 3 metres
of the solar inverter.
Mechanical load-bearing capacity
Note during installation that the solar
inverter weighs 30 kg. The installation
surface must be firm and able to carry
this weight in the long term.
Thermal interaction
The installation surface must consist of
flame-retardant material (not suitable:
surface of wood or plastic; suitable: con-
crete and masonry), as the frame of the
solar inverter can heat up to a maximum
of 70°C.
A minimum distance of 300 mm to other
units, cabinets, ceilings, cable ducts,
etc. must be maintained above, below
and to the sides of the housing.
See the figure Requirements for installa-
tion location.
The solar inverter must be installed verti-
cally to enable sufficiently free convec-
tion.
Several solar inverters may not be mount-
ed over each other to prevent them from
heating each other.
Summary of Contents for AT 2700
Page 1: ...User Manual for Sunways Solar Inverter AT 5000 AT 4500 AT 3600 AT 2700...
Page 8: ...1 0 Product Description...
Page 16: ...16 2 0 Safety precautions...
Page 22: ...22 3 0 Installation...
Page 46: ...46 4 0 Commissioning...
Page 56: ...56 5 0 Operation...
Page 96: ...96 6 0 System monitoring...
Page 129: ...129...
Page 130: ...130 7 0 Appendix...
Page 135: ...135 Efficiency of AT 5000 Output power W...
Page 136: ...136 Efficiency of AT 4500 Output power W...
Page 137: ...137 Efficiency of AT 3600 Output power W...
Page 138: ...138 Efficiency of AT 2700 Output power W...
Page 140: ......
Page 141: ...C F Werbung und Dokumentation Villingen Schwenningen www cundf de...