33
Grid connection
!
Extreme danger from electric shock!
Touching live parts can result in death.
All electrical work must be conducted by
a qualified electrician while observing
the VDE regulations, national and other
regulations!
Observe the pin assignment of the AC
bayonet connector. An incorrect assign-
ment can result in the unit being de-
stroyed.
No consumers may be connected to the
supply line from the solar inverter to the
mains fuse.
Always separate the solar generator
side first by quickly opening the DC load
break switch and then the grid connec-
tion by switching off the corresponding
mains fuse.
If the voltage on the AC connection ex-
ceeds the permissible value due to a long
line length or an insufficient cable cross-
section, the solar inverter will discon-
nected from the grid. In power grids with
a low output and a high solar generator
output, this can lead to individual solar
inverters being switched off and then on
again several times.
Survey
The grid connection of the solar inverter
is made via an AC bayonet connector on
the underside of the unit. With a 3-phase
feed point (3-phase AC connection), a 5-
wire connection (L1, L2, L3, N, PE) is used
due to the 3-phase passive grid monitor-
ing, while only a 3-wire connection (L1,
N, PE) is used on the single-phase feed
point. Feeding is always single-phase via
AC terminal 2.
Summary of Contents for AT 2700
Page 1: ...User Manual for Sunways Solar Inverter AT 5000 AT 4500 AT 3600 AT 2700...
Page 8: ...1 0 Product Description...
Page 16: ...16 2 0 Safety precautions...
Page 22: ...22 3 0 Installation...
Page 46: ...46 4 0 Commissioning...
Page 56: ...56 5 0 Operation...
Page 96: ...96 6 0 System monitoring...
Page 129: ...129...
Page 130: ...130 7 0 Appendix...
Page 135: ...135 Efficiency of AT 5000 Output power W...
Page 136: ...136 Efficiency of AT 4500 Output power W...
Page 137: ...137 Efficiency of AT 3600 Output power W...
Page 138: ...138 Efficiency of AT 2700 Output power W...
Page 140: ......
Page 141: ...C F Werbung und Dokumentation Villingen Schwenningen www cundf de...