OUTDOOR GRAPH (see also next page)
P5 AC
Heat curve minimum outdoor temperature (°C)
This sets the minimum outdoor temperature at which one wants the maximum flow temperature that is set.
P5 AD
Heat curve flow temperature at minimum (°C)
This sets the desired maximum flow temperature at the set minimum outdoor temperature.
P5 AE
Heat curve maximum outdoor temperature (°C)
This sets the maximum outdoor temperature at which one wants the minimum flow temperature that is set.
P5 AF
Heat curve flow temperature at maximum (°C)
This sets the desired minimum flow temperature at the set maximum outdoor temperature.
P6 BC
Heat curve parallel shift (°C)
The heating curve is set by the parameters. Next to these setting done by the installer, the end user has the free-
dom to influence the flow temperature by doing a parallel shift setting. In this parameter the margins are set within
which the user can increase and decrease the calculated flow temperature relative to the calculated flow tempera-
ture by the heating curve that is set.
The actual parallel shift that is set by
the user within the bandwidth allowed according to “P5 AQ Max heat curve
parallel s
hift”.
Additional settings of the heating curve p.t.o.
OUTDOOR TEMPERATURE
FLO
W
T
E
M
P
E
R
A
TU
R
E
40
30
20
10
-40
-30
-20
0
-10
30
0
90
80
70
60
50
40
20
10
P5 AE
outdoor temp high
P5 AC
outdoor temp low
P5 AF
- Flow temp at
outdoor temp high
P5 AD
- Flow temp at outdoor temp low
P6 BC
- Parallel shift
HEATING CURVE
- main settings