S-CB
+
Boiler Range Manual
48
SCREEN:
11
C a s c D e s i g n
0
0 = MASTER, 1 ..... 11 = SLAVES
C a s I n f
0 1 2 3 4 5 6 7 8 9 A B
Displays number, priority and state of cascade boilers.
DESCRIPTION "CASCINFO"
Screen 11
Shows the number of boilers connected with the cascade. The Master/Lead boiler is designated as 0.
Slave/Lag boilers will be designated 1, 2, 3, 4, 5,
6, 7, 8, 9, A, B. When a “-“ is used instead of a number, then
that boiler is either not connected, or in a lockout mode and not available for the c
ascade. When an “x“ is used
instead of a number, then that boiler is connected, but in lockout mode.
When a
“d” is displayed instead of a number, then that boiler is handling a DHW demand.
When the number is flashing, then that boiler is providing heat to the cascade. When the leading boiler is
changed according to the set priority change time, then that boiler
’s address will be shown first in the row of
numbers.
Example 1: "3 4 5 - - - - - - 0 1 2"
Six are boilers present and nr. 3 has priority.
Example 2: "3 4 x - - - - - - d 1 2"
Six boilers are present and nr. 3 has priority. Boiler 0 is heating up an indirect DHW tank. Boiler 5 is present,
but in a lock-out.
SCREEN:
12
C a s c P o w e r 9 9 9 % 9 9 9 %
% heat demand of total (cascade) power available (%).
D u a l
B u r n e r :
N o
Heat exchanger equipped with two burners: "Yes" or "No".
SCREEN:
13
M a x T h e r m
O p e n
Status of the maximum thermostat: "Open" or "Closed".
G e n B l o c k
C l o s e d
Status of the general blocking contact: "Open" or "Closed".
SCREEN:
14
S i p h o n p r e s s
C l o s e d
Status of the siphon pressure switch: "Open" or "Closed".
N R V C o n t a c t
O p e n
Status of the non-return valve contact: "Open" or "Closed".