S-CB
+
Boiler Range Manual
45
By pressing (◄ ►) one
can toggle though the
available menus.
"USER LOCK" menu
In this menu one can lock the menu
for users
0= UNLOCKED
1= LOCKED
When un-locked the user can enter
the "MENU" by pressing the menu
button and all submenus will show.
When locked the user has to push
the : MENU and simultaneously
press ▼ for six seconds to get ac-
cess to all submenus.
This is to prevent accidental changes!
NOTE: The parameters sub menu
can always be accessed.
"MAINTENANCE" menu
By pressing (
◄ ► ) one can set the
following options:
- Maintenance reset
- Maintenance Mode
- All
- Date
- Ignition cycles
- Burning hours
- Mainten Off
"SETPOINT" menu
In this menu one can change tem-
perature settings without the need for
a password.
-
Heating set point
Flow set point when controlling on/off
on set flow temp.
-
Heating reduced
The amount of degrees diff. relative
to "Heating set point" during night
reduction.
-
Parallel shift +/- relative to out-
door curve
(also in outdoor menu possible)
-
Hot water set point
Calorifier or Water heater (depends
on heater type)
-
Hot water reduced
The amount of degrees diff. relative
to "Hot water set point" during night
reduction.
"PROGRAM" menu
In this menu one can set the CH,
DHW and Anti Legionnella program.
"OUTDOOR" menu
In this menu one can set all Outdoor
relevant parameters.
"OPERATING HISTORY" menu
Shows burning hours DHW, Heating,
etc.
"FAULT HISTORY" menu
press:
▼ Reading last fifteen faults
(only reading!).
"TIME/DATE/DAY" menu
In this menu one can set the time and
the date.
"PARAMETERS" menu
In this menu one can change param-
eters. The possible access
depends on the password that is
used.
HOW TO CONFIRM CHANGES
When changes have been made in one of the nine menus below,
the user presses ENTER to confirm these changes.
To prevent anyone from making changes by mistake, the following
happens when changes are made:
Step 1:
The user presses [ENTER] to confirm the change made
or [MENU] to exit the menu without changes. HINT: First pro-
gramme all changes planned, then only after that, press [ENTER]
Step 2:
The display asks the user to be sure to make these
changes. The user can cancel or confirm by using the left and right
arrows.
CANCEL =
◄
CONFIRM =
►
Enter password
Enter PW
Level 1:
three second message
confirming access:
LEVEL 1
Enter PW
Level 2:
three second message
confirming access:
LEVEL 2
parameter menu
Summary of Contents for S-CB+ Series
Page 2: ......
Page 3: ......
Page 22: ...S CB Boiler Range Manual 22 ...
Page 39: ...S CB Boiler Range Manual 39 9 4Electrical schematics ...
Page 124: ...S CB Boiler Range Manual 124 ...